11.6.2 Programming an alarm function block to trigger notifications

To add an alarm function block, start by selecting the device you want in the starting
window and then clicking on the "Programming" button at the bottom left.
A dialog box in which you can select the programming language you want will appear.
Select the programming language you want.
Once you make your selection, the Programming view will appear.
Go to the list on the left side and look for the "Other function blocks" folder. The alarm
function block that uses the e-mail function will be found there.
Select the alarm function block and drag it to the white canvas at the top right.
Now click on the alarm function block. The corresponding parameters will appear
at the bottom.
Use the "AL" drop-down menu to assign a number to the function block. You can also
add a comment in the field to the right of the drop-down menu.
The purpose of the "Function block release by EN is necessary" checkbox is to define
whether the alarm function block should be enabled and disabled based on the EN input.
Do not enable this option if you want the alarm function block to always be enabled.
You can use the "Webserver active as long as there is a state of 1 at input EN" check-
box to define whether the web server in the easyE4 should be active as long as EN is
active.
Use the "Parameter display" drop-down menu to select the "Call enabled" or "Call dis-
abled" option.
Finally, select the "Type of information transmission" and "Recipient assignment"
options you want and enter the subject and message that should be sent by e-mail.
See also
→ Section "AL - Alarm function block", page 349