The function block and its parameters
Function block inputs
Description
(Bit)
EN
1: Activates the function block.
(DWord)
I1
Input value
TG
Recovery time TG [0.1 s]
KP
Proportional gain Kp [%]
Value range: 0 ... 65535
Assigning operands
You can assign the following operands to the function block inputs that are numeric
inputs.
Operands
Constant, timer constant
MD, MW, MB - Markers
NB, NW, ND - NET markers
nNB, nND, nND- NET markers
NET stations n
IA - Analog input
QA - Analog output
QV - QV - Numeric output of a FB
You can assign the following operands to the function block inputs that are bit inputs:
Operands
Constant 0, constant 1
M – Markers
RN - Input bit via NET
SN - Output bit via NET (send)
N - Net marker bit
nN - NET marker bit NET station n
ID: Diagnostic alarm
LE - Output backlight
P buttons
I - Bit input
Q - Bit output
Q - Bit output of a FB
easyE4 11/18 MN050009 EN www.eaton.com
6.1 Manufacturer function blocks
Note
Value range: -32768...+32767
Value range: 0...65535
The value 10 corresponds to a recovery
time of 1000 ms.
Value range: 0...65535
The value 100 corresponds to a KP
(factor) of 1.
The value 50 corresponds to a KP of 0.5.
Value inputs
x
x
x
x
x
x
x
Bit inputs
x
x
x
x
x
x
x
x
x
x
x
x