2.5 Introduction to Programming

The FP-5000 can be programmed using an HMI with PowerPort™
software through the RS-232 serial port or remotely via the rear
INCOM PN using PowerNet. In addition, the FP-5000 may be
programmed directly from the front panel. We will focus on direct
programming from the front panel in this Quick Start Section.
Programming is restricted to authorized users through password
protection and through the physical restraint of a security door
which may be sealed with a lead seal.
CAUTION
CHANGING THE SETTINGS OF THE FP-5000 WILL
SUBSTANTIALLY IMPACT SYSTEM OPERATION. ONLY
AUTHORIZED PERSONNEL WHO ALSO POSSESS THE PASS-
WORD MAY MAKE MODIFICATIONS TO THE FP-5000 SET-
TINGS.

2.5.1 Entering Set (Programming) Mode

Lift the security door cover over the Set and
Test buttons on the front panel and press the
Set pushbutton. The Set LED (at the upper right
Set
corner of the Set pushbutton) will illuminate
and the display will change to the Password
request Window. Unauthorized programming is
prevented by password protection and by
means of the security door over the Set
pushbutton, which may be secured with the
lead seal, making apparent any programming
access. Minimal programming will be described
in this Quick Start section. Please refer to the
complete programming instructions in Setting
the FP-5000, Section 5.

2.5.2 Password

The Setting Mode from the Front Panel is password protected to
prevent access by unauthorized users. In order to access the
programming mode of the FP-5000 a password must be entered.
Each Password is a 4-character alphanumeric value. The FP-5000
is shipped with the password protection effectively disabled, set
to the default of '0000'. Entering Program Mode (or Test Mode) with
acceptance of the default password is done by pressing the Enter
button with the 4-asterisk Password display unchanged. Each
character in the Password may be modified to any of the charac-
ters 0-9 and A-Z within program mode.
Password Window
Single Arrow For Bit
Dual Arrow for Value
If the password has not been changed previously, press enter, the
password default is zero (0).
If a password has been previously programmed, use the
and
pushbuttons to select which of the 4 password
characters to change, the
the appropriate character in each location, and the
pushbutton to enter the specified password.
Page 2-6
[****]
and
pushbuttons to change to
Enter
For more information visit:
FP-5000
KEEP YOUR PASSWORD SECRET AND RECORD IT IN A SAFE
PLACE. IF THE PASSWORD IS LOST, A NEW PASSWORD MAY
BE ENTERED DURING THE FIRST 2 MINUTES AFTER CON-
TROL POWER IS APPLIED TO THE FP-5000.

2.5.3 Navigation Within Settings Mode

The FP-5000 parameters that are set are either
numeric or elements of a list.
Use the Enter pushbutton to select the settings
category or value to update. The Enter
pushbutton also verifies the updating of
Enter
settings upon exiting Set mode.
Use the Up and Down pushbuttons to
increment or decrement setting values one step
at a time or to step forward and backward
through a presented list of settings.
Use the Page Up and Page Down
pushbuttons to increment or decrement setting
values 10 times as fast as with the Up and Down
pushbuttons, or to step forward or backward
through a list of settings a page at a time.
Use the Previous pushbutton to back out of
the settings menu. However, when the "Save
Settings Window" appears, Enter must be
pressed in order to accept and save your
Previous
setting changes. If the Previous pushbutton is
pressed again, all your changes will be
discarded. Numeric ranges are looped so that
going past one end of an interval brings you to
the beginning of the other end of the range for
the setting. Similarly, lists are also looped.
Upon entry to the Set Function, the user will
view the Setting Main Screen where the
selections will be seen three at a time using the
up and down navigation pushbuttons.
www.eatonelectrical.com
CAUTION
Setting Main
System Config
Protection
System Alarms
Logging
Contact Input CFG
Output Config
Programmable Logic
Cold Load Pickup
Clock
Communications
Change Password