C C h h a a p p t t e e r r 8 8 C C o o m m m m u u n n i i c c a a t t i i o o n n
This chapter describes the communication features of the Eaton Power Xpert 9395C UPS system and provides
information about connecting hardware. For terminal wiring information, see paragraph
3.2.5 UPS System Interface Wiring Preparation
of the customer interface panels and terminals, see
8 8 . . 1 1
X X - - S S l l o o t t C C a a r r d d s s
The Eaton 9395C UPS system has four standard, factory-installed X-Slot communication bays. See
for bay locations. The UPS is compatible with the following X-Slot cards (see
Power Xpert® Gateway Card - provides a data gateway from the UPS to the Power Xpert software;
provides remote monitoring through a Web browser interface, e-mail, and a network management system
using SNMP; connects to a twisted-pair Ethernet (10/100BaseT) network. Modbus TCP support provides
direct integration of the UPS parameters to a Building Management System (BMS). It has a built-in
switching hub that allows one additional network device to be connected to the network without the
requirement of an additional network drop.
Modbus Card - provides direct integration of UPS information (meters and status) to a Building
Management System (BMS) using the Modbus RTU protocol.
Relay Interface Card (AS/400) - has isolated dry contact (Form-C) relay outputs for UPS status: Utility
failure, Low battery, UPS alarm/OK, or On bypass when interfacing with IBM AS/400 computers, other
relay connected computers, and industrial applications.
Industrial Relay Card (IRC) - indicates the operating status of the UPS system using the customer's
monitoring equipment. The IRC uses four isolated normally-open or normally-closed dry relay contacts to
indicate the UPS status. Online, Bypass, Battery, and Alarm modes can be monitored.
Powerware Hot Sync CAN Bridge Card - provides connectivity for operational mode control and metering
of a parallel system at any UPS in the system. In addition, this card can be used to connect optional system
monitoring devices, such as a Remote Monitor Panel II (RMP II), a Relay Interface Module II (RIM II), or a
Supervisory Contact Module II (SCM II) to the UPS.
LAN drops for use with X-Slot connectivity cards must be provided by facility planners or the customer.
For installation and setup of an X-Slot card, contact an Eaton service representative (see para.
Refer to the manual supplied with the X-Slot card for user instructions.

Figure 105. Optional X-Slot Cards

Modbus Card
Relay Interface Card
Power Xpert Gateway Card
8 8 . . 2 2
P P r r e e d d i i c c t t P P u u l l s s e e
The Eaton 9395C UPS supports Eaton's. PredictPulse Remote Monitoring and Management Service is a
subscription monitoring and management service that collects and analyzes data from connected power
and paragraph
Figure 27
Hot Sync CAN Bridge
Card
Industrial Relay Card
Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821—Rev 06
4.7 Installing Interface
Connections. For location
and
Figure 31
through
Figure
Figure
105):
34.
Figure 31
1.7 Getting
Help).
139