oad protection switch (AC disconnect switch)
To protect the inverter and the AC connection line, a device must be in-
stalled to protect against maximum current and leakage to ground, with
the following characteristics:
Magnetic protection char-
In case of installation of a residual current protection device must meet
the following characteristics:
Differential protection type
I
nstallation of the cable on the AC output connector
To avoid risks of electrical shock, all wiring operations must be carried out with the disconnect
switch downstream of the inverter (grid side) opened and applying LOTO procedure on it.
and subsequently loosen the cable gland.
1
Ensure that the cable's radius of curvature is more than 4 times the
diameter of the cable
REACT2-UNO-3.6
Type
Voltage rating
Current rating
acteristic
REACT2-UNO-3.6
Differential sensitivity
Number of poles
2
1
- 77 -
5 - Installation
REACT2-UNO-5.0
Automatic circuit breaker
with thermal-magnetic protection
230 Vac
25 A
32 A
B/C
REACT2-UNO-5.0
A/AC
300 mA
2
2a
2
2b