- Error code
- Error message
Name of Alarm and Cause
- Warning
E068
Overcurrent of "battery charger" ("Charger"
- Charger - OC
circuit):
-
(On)
Error inside the charger (battery unit).
E069
Error internal to battery unit charger circuit
- Charger-SlowRamp
("Charger" circuit").
-
(On)
E070
- Charger-preChar.
Error inside the charger (battery unit).
-
(On)
E077
- Internal Error
Error inside the inverter
-
(On)
E078
Riso test error:
- Riso Test fail
Problem detected during the Riso test phase.
-
(On)
E084
The error occurs if the input voltage is particularly low
- BackFeed OC
(typically in the evening in conditions of low irradiation)
-
(On)
and indicates a return current from the inverter to the
photovoltaic panels).
E086
Error battery unit 1 unusable:
- Batt. 1 - F2
Indicates that the battery unit is unusable and must be
-
No Icon
replaced.
E087
Error battery unit 2 unusable:
- Batt. 2 - F2
Indicates that the battery unit is unusable and must be
-
No Icon
replaced.
E088
Error battery unit 3 unusable:
- Batt. 3 - F2
Indicates that the battery unit is unusable and must be
-
No Icon
replaced.
E089
Incorrect grid wiring connection on Backup output:
- Wrong Wiring
The error occurs if the grid cables have been
-
(On)
incorrectly connected to the Backup output.
Battery under voltage:
E096
The voltage of the battery is too low and need to be
- CHARGER - battery UV
charged. In this condition the discharge of the battery
-
(On)
is disabled.
E097
- CHARGER - battery HW
Error inside the battery unit.
-
(On)
Solution
externally.
- If the problem persists, contact customer assistance.
externally.
- If the problem persists, contact customer assistance.
externally.
- If the problem persists, contact customer assistance.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
If the error occurs in the evening or in conditions of low
irradiation, it must not be considered a problem but a
- If the error occurs with good irradiation conditions, switch
the inverter off and back on again; if the error persists, contact
customer assistance.
If the problem (once the system has been switched off and
back on) persists, contact customer assistance.
If the problem (once the system has been switched off and
back on) persists, contact customer assistance.
If the problem (once the system has been switched off and
back on) persists, contact customer assistance.
installed correctly.
condition will allow it.
If the problem (once the system has been switched off and
back on) persists, contact customer assistance.
- 145 -