- Web server message
Name of Derating and Cause
- Warning
Power limitation due to excess temperature:
The message indicates that a power limitation is active since
an excess temperature condition has been recorded inside the
inverter (This parameter depends also on the power which the
inverter must provide since the measurement of temperatures is
- LIMxxx% CODE:05
components of the inverter itself).
LIM xxx% = Power reduction percentage
Examples:
LIM 100% = no power limitation
LIM 50% = limitation to 50% of the output nominal power
Power limitation due to input overvoltage:
The message indicates that a power limitation is active since an
input overvoltage (DC) has been recorded.
- LIMxxx% CODE:06
LIM xxx% = Power reduction percentage
Examples:
LIM 100% = no power limitation
LIM 50% = limitation to 50% of the output nominal power
Solution
sunlight. Wait for the temperatures to which the
inverter is exposed to return to the operating range
and for the inverter to cool down.
- If the problem persists (once the ambient
temperature has returned to within the range),
contact customer assistance.
the inverter with a voltmeter.
- If it is higher than the maximum voltage of the
operating range, the alarm is genuine and it is
generator. If the voltage has also exceeded the
maximum input threshold the inverter could be
damaged.
- If it is lower than the maximum voltage of the
operating range, the alarm is caused by an internal
malfunction and it is necessary to contact customer
assistance.
- 147 -