ABB REACT 2 Series Product Manual page 109

Solar inverter
Hide thumbs Also See for REACT 2 Series:
Table of Contents

Advertisement

Battery
- Battery Type. Select REACT2-BATT.
- Number. Set the number of REACT2-BATT (battery unit)
installed.
Energy Policy
- Energy Policy: set the way to manage the energy produ-
ced by the PV plant, choosing from the following:
Management
Description
mode
The system automatically manages
tion of energy to the grid. If the meter is
Zero injection
disconnected or not working the inver-
ter's output power is restricted to zero
in order to avoid accidental power fee-
ding to the grid.
The system automatically manages
Self consumption
consumption. All unused power from
domestic loads will feed into the grid.
The system automatically manages
the grid with power greater than: PDC
x Plim
where PDC is the power of the pho-
tovoltaic generator ("PV GENERA-
TOR POWER" parameter) and Plim is
the output power limit with respect to
PDC(%) ("FEED-IN POWER" parame-
Custom
ter).
- PV Generator Power (Wp): Insert the
power value of the photovoltaic sy-
stem installed.
- Feed-in Power (% PV Generator Po-
wer): Set the percentage AC power
restriction (with reference to the value
of the photovoltaic system (kWp) in-
stalled) to be feed into the grid.
- Backup Mode:
Set the way to manage the backup funtionality, choosing from:
AUTO. The necessary condition for activating the backup
function is the lack of grid.
External Control. The backup function is controlled by an
external command.
- 109 -
7 - Operation
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

React2-uno-3.6-tlReact2-uno-5.0-tl

Table of Contents