ABB REACT 2 Series Product Manual page 142

Solar inverter
Hide thumbs Also See for REACT 2 Series:
Table of Contents

Advertisement

- Error code
- Error message
Name of Alarm and Cause
- Warning
"Bulk" over-voltage (DC-DC circuit):
- E004
Error inside the inverter. The alarm is raised when the
- Bulk OV
voltage at the heads of the bulk capacitors exceeds
-
(On)
the Over Voltage threshold (internal unchangeable
threshold).
Communication error inside the inverter:
- E005
The alarm occurs when there are communication
- Comm.Error
problems between the control devices inside the
-
(On)
inverter.
Output overcurrent:
- E006
The alarm occurs when the inverter's output current
- Output OC
exceeds the inverter's threshold for maximum output
-
(On)
current.
- E007
Saturation recorded on the IGBT components:
- IGBT Sat
The alarm appears when one of the active devices of
-
(On)
the inverter is in saturation state.
Low "Bulk" voltage (DC-DC circuit):
The alarm can be caused by causes external to
- E010
the inverter: a reduced input voltage on the inverter
- Bulk Low
(just above the activation voltage) but which is not
-
(On)
the photovoltaic generator (typical condition of the
stages with limited irradiation)
- E011
Long wait for "Booster" regime to start:
- Ramp Fail
Error internal to inverter relating to start up time for
-
(On)
DC-DC circuit regime (Booster)
Error in the "Booster" circuit (DC-DC side)
- E012
recorded by the "Inverter" circuit (DC-AC side):
- DcDc Fail
Error inside the inverter regarding the operation of the
-
(On)
DC-DC circuit part (Booster).
rather than independent):
- E013
The alarm is generated solely when the inverter
- Wrong Mode
-
(On)
each of the two channels and if the two voltages differ
by more than 20Vdc, the alarm is raised .
Excessive temperature inside the inverter:
External temperature over 60°C. This parameter also
- E014
depends on the power which the inverter must supply
- Over Temp.
since the measurement of temperatures is done
-
(On)
the components of the inverter itself
- E015
Fault recorded on the "Bulk" capacitor:
- Bulk Cap Fail
Error inside the inverter regarding a problem in the
-
(On)
bulk capacitors.
Error in the "Inverter" circuit (DC-AC side)
- E016
recorded by the "Booster" circuit (DC-DC side):
- Inverter Fail
The alarm is generated when a problem is detected in
-
(On)
the inverter circuit part (DC/AC).
parallel inputs. In this particular
input voltage of
- 142 -
Solution
The alarm may be triggered by causes external to the
inverter:
- An excessive input voltage can be recorded as a condition
for bulk over voltage. In this case it is advisable to check
the inverter's input voltage and should this value be close
photovoltaic generator.
- Excessive grid voltage could cause the bulk voltage to rise in
uncontrolled fashion with a consequent protection intervention
and hence generation of the alarm. In these cases the alarm is
transitory and the inverter automatically restarts
- The alarm may be triggered by causes inside the inverter
and in this case it is necessary to contact customer
assistance.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
Once the error appears, the inverter attempts to resume
normal operation.
- Should the error occur sporadically, it may be caused by a
brusque transition of the grid voltage or of the input voltage,
but is not due to a malfunction by the inverter.
- If the error is connected to an internal fault, it will continue to
appear and so it is necessary to contact customer assistance.
- If the error signal occurs sporadically, it may be due to
causes external to the inverter (limited irradiation and so
limited power availability from the PV generator).
- If the problem occurs systematically even in conditions of
high irradiation and with
higher than the activation voltage, contact customer
assistance.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
set to "PAR" and that the jumpers between the two input
channels have been included.
input strings have the usual number of standard panels of the
usual brand and with the same inclination/orientation.
of the
customer assistance.
for the temperatures to which the inverter is exposed to return
to the operating range and for the inverter to cool down.
- If the problem persists (once the ambient temperature has
returned to within the range), contact customer assistance.
You must remember to wait for the time necessary to allow the
inverter to cool down.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
8 - Maintenance