Data of the TOP Control Continuous

OPERATING CONDITIONS
Permissible ambient temperature
Protection type
cable or
ATTENTION!
CONFORMITY TO THE FOLLOWING STANDARDS
CE
MECHANICAL DATA
Dimensions
Housing material TOP Control
Dichtmaterial
ELECTRICAL DATA
Connections
Voltage supply
Power consumption
Housing internal temperature
indication
Input resistance for
actual value signal
Input resistance for
setpoint signal
Protection class
Analog position feedback:
max. current
for voltage output 0 ... 5/10 V
max. burden
for current output 0/4 ... 20 mA
Inductive proximity switch
current limitation
The TOP Control Continuous is not suitable for outdoor use.
conformity wer. EMC Guideline 89/336/EWG
see data sheet
outer: Noryl (PPE/PA), PSU, inner: PA 6
NBR
Choice between multipole connector or
3 bushings M 16 x 1.5
with screw terminals 0.14 ... 1.5 mm²
24 V DC ± 10 %
residual ripple 10 %
No industrial DC!
< 5 W
- 55 ... + 125 °C, accuracy ± 2 °C
180 Ω at 4 - 20 mA/resolution 12 bit
17 kΩ at frequency, 0 ... 1000 Hz / 1‰ of mean
> 300 V
PT-100 - 20 ... + 220 °C, resolution < 0.1 °C
180 Ω at 0/4 - 20 mA/resolution 12 bit
19 kΩ at 0 - 5/10 V /resolution 12 bit
3 to VDE 0580
10 mA
560 Ω
100 mA
- 10 ... + 50 °C
IP 65 to EN 60529
sinus, square-wave, sawtooth
ss
S
D
YSTEM
ESCRIPTION
(only with correctly connected
plug and socket)
8630 - 31