AINTENANCE AND ERROR CORRECTION ON THE PROCESS CONTROLLER

Maintenance

When operated according to these Operating Instructions, the TOP Control Continuous is
maintenance free.
Error messages and malfunctions
Error messages on the LC display
General error messages
Display
CMD FAUL
SP FAULT
PV FAULT
PT FAULT
P1 FAULT
P2 FAULT
TMP FAUL
EE FAULT
MFI FAUL
Error messages on execution of the function X.TUNE
Display
X.ERR 1
X.ERR 2
X.ERR 3
X.ERR 4
X.ERR 6
X.ERR 7
154 - 8630
Causes of error
signal error
set-value, positioner
signal error
set-value, process controller
signal error
actual value, process controller
signal error
actual value, Pt-100
signal error
actual value, P1 fluid flow controller
signal error
actual value, P2 fluid flow controller
signal error
actual value, temperature, fluid flow controller
EEPROM faulty
Fieldbus board faulty
Causes of error
No compressed air connected
Compressed air failure during
AUTOTUNE
Actuator or positioning system leaky
on exhaust side
Actuator system leaky on pressurized
side
The end positions for POS-MIN and
POS-MAX are too near to each other
False allocation of POS-MIN and POS-
MAX
Remedy
check signal
check signal
check signal
check signal
check signal
check signal
check signal
none, device faulty
Remedy
Connect compressed air
Check compressed air supply
None, device faulty
None, device faulty
Check whether the allocation of the end
positions to POS-MIN and POS-MAX via
the function TUNE-POS is correct.
If incorrect:
Execution TUNE-POS again.
If correct:
TUNE-POS with this arrangement of the
end positions is not possible since they
are too close together.
To determine POS-MIN and POS-MAX,
move the actuator in each case in the
direction shown on the display.