Choice Of Binary Outputs Or Process Value Input - Burkert 8630 Operating Instructions Manual

Top control continuous
Hide thumbs Also See for 8630:
Table of Contents

Advertisement

I
NSTALLATION

Choice of binary outputs or process value input

➔ Select using the jumpers:
2 binary outputs (see terminal Allocation when binary outputs selected ) or
Process value input (see terminal Allocation when process value input selected ).
Terminals 7 to 10 are connected to the corresponding signals.
Jumper
Terminal
7
8
9
10
Terminal allocation on selection of process value input:
➔ The input type is set via the configuration menu (see Procedure for specifying the basic settings ).
Input type*
Jumper Terminal Allocation
4 ... 20 mA
internal
supply
Frequency
internal
supply
4 ... 20 mA
external
supply
Frequency
external
supply
Pt-100
(see
Note
below)
For reasons of line compensation, connect the Pt 100 sensor over 3 conductors. Be sure
NOTE
to bridge terminals 9 and 10 at the sensor.
48 - 8630
Allocation
Binary output 1
Binary output 1
Binary output 2
Binary output 2
7
+ 24 V input transmitter
8
Output transmitter
9
Bridge to GND (GND from
3-conductor transmitter)
10
GND
7
+ 24 V supply sensor
8
Clock input +
9
not connected
10
Clock input - (GND)
7
not connected
8
Process actual +
9
Process actual -
10
not connected
7
not connected
8
Clock input +
9
not connected
10
Clock input -
7
not connected
8
Process actual 1 (current supply)
9
Process actual 2 (compensation)
10
Process actual 3 (GND)
External connection
7
24 V / 0 V
GND
8
24 V / 0 V
9
10
GND
External connection
7
8
9
10
7
8
10
8
9
8
10
8
9
10
NC / NO
NC / NO
+24 V
Clock +
Clock - (GND)
+ (4 ... 20 mA)
GND
Clock +
Clock -
Pt100