* Electrical connection - terminals for cable bushing
ATTENTION!
For connection to the technical earth (ground) (TE), a threaded stud with nut is
provided on the connection module. To assure electromagnetic compatibility
(EMC), connect this stud to a suitable earthing (grounding) point using as short a
cable as possible (max. 30 cm).
Use of the 4 - 20 mA setpoint input
NOTE
If the voltage supply of a TOP Control Continuous device fails in a row of such devices
connected in series, the input of the failed device will become high-impedance. This will
cause the 4 - 20 mA standard signal to fail. If this occurs, please contact Bürkert Service
directly.
Connection PCB of the TOP Control Continuous with screw
terminals and jumpers
Terminal configuration with cable bushings
Terminal
Allocation
1
Setpoint +
2
Setpoint GND
3
Analog position feedback +
4
Analog position feedback GND
5
Operating voltage +
6
Operating voltage GND
➔ Remove the cover with the cable bushings to gain
access to the screw terminals. This is done by
unscrewing the 4 self-tapping screws.
External connection
1
+ + (0/4 ... 20 mA or 0 ... 5/10 V
2
GND
3
+ (0/4 ... 20 mA or 0 ... 5/10 V)
4
GND
5
6
I
NSTALLATION
completely isolated electrically
24 V DC ± 10 %
max. residual ripple 10 %
8630 - 47