Operation As A Flow Rate Controller (Option); Characteristics Of The Flow Rate Controller Software - Burkert 8630 Operating Instructions Manual

Top control continuous
Hide thumbs Also See for 8630:
Table of Contents

Advertisement

* Operation as a flow rate controller (option)

The flow rate controller is a special type of process controller. The process value (PV) is not measured
directly via an analog input but calculated in the device by the dp method. According to the algorithm,
the flow rate is dependent on the parameters pressure before valve (p1), pressure after valve (p2), me-
dium temperature (T) and the kv value. For this reason, the TOP Control Continuous FMR has inputs
for 2 pressure transmitters and a temperature transmitter which can be optionally connected.
One pressure transmitter measures the pressure before the valve and a second one after the valve. The
temperature is either entered manually in the operating menu or is provided as a standard signal by a
temperature transmitter. The kv value is determined internally from the current position of the control
valve. For this purpose, a kv characteristic curve is provided in the control valve used.
The density of the medium is entered via the operating menu.
Temperature (optional)
T
In the case of the flow rate controller, the process parameters are either the volumetric flow rate or, for
special applications, the transport velocity at the end of a pumping section.
The volumetric flow rate is represented in m
gas pressure of 1013 mbar (abs).
There are special applications for flow rate controllers in which a pumping section is set up after the
valve, in which bulk goods enter via an airlock. These bulk goods are blown through the pumping
section by the pumping pressure that builds up behind the valve.
The transport velocity corresponds to the volumetric flow rate of the medium, referred to the piping
diameter of the pumping section. However, it is not specified for standard conditions, but reflects the
velocity of the gas particles at the existing medium temperature. The diameter is entered in the
operating menu.

Characteristics of the flow rate controller software

The flow rate controller offers the same functions as the process controller.
Pressure
PV
p1
8630
Flow rate
controller
e.g. valve
type 2712
kv value
p1
3
/h STP, i.e. referred to 0 °C (medium temperature) and a
Pressure
p2
p2
S
D
YSTEM
ESCRIPTION
8630 - 25