Maintenance - Burkert 8630 Operating Instructions Manual

Top control continuous
Hide thumbs Also See for 8630:
Table of Contents

Advertisement

M
AINTENANCE AND ERROR CORRECTION ON THE POSITIONER

Maintenance

When operated according to these Operating Instructions, the TOP Control Continuous is
maintenance free.
Error messages and malfunctions
Error messages on the LC display
Error message on switching on
Display
CMD FAUL
EE FAULT
Error message on execution of the function X.TUNE
Display
X.ERR 1
X.ERR 2
X.ERR 3
X.ERR 4
X.ERR 6
X.ERR 7
Other malfunctions
Problem
POS = 0 (with CMD > 0 %) or
POS = 100 %, (by CMD < 100 %)
152 - 8630
Causes of error
signal error
set-value positioner
EEPROM faulty
Causes of error
No compressed air connected
Compressed air failure during
AUTOTUNE
Actuator or positioning system leaky
on exhaust side
Actuator system leaky on pressurized
side
The end positions for POS-MIN and
POS-MAX are too near to each other
False allocation of POS-MIN and POS-
MAX
Possible causes
Tight-closing function
(CUTOFF)
has been inadvertently activated
Remedy
check signal
none, device faulty
Remedy
Connect compressed air
Check compressed air supply
None, device faulty
None, device faulty
Check whether the allocation of the end
positions to POS-MIN and POS-MAX via
the function TUNE-POS is correct.
If incorrect:
Execution TUNE-POS again.
If correct:
TUNE-POS with this arrangement of the
end positions is not possible since they
are too close together.
To determine POS-MIN and POS-MAX,
move the actuator in each case in the
direction shown on the display.
Remedy
Deactivate tight-closing
function

Advertisement

Table of Contents
loading