DataView™ LI55 Level Controller
7.
The display moves to the high input calibration (C Hi). Apply the high
input signal and press Enter.
8.
Set the display for the high input calibration, in the same way as it was
set for the low input calibration, typically 20.000 mA.
ENTER
The graphic above shows the calibration of the current input. The voltage input is
calibrated in a similar way.
Tips:
Low and high input signals can be any valid values within the range of
the meter.
Observe minimum input span requirements between input 1 and input
2.
Low input should be less than high input signal.
MN301033 Rev B1
ENTER
Instruction Manual
ENTER
ENTER
ENTER
87