Monitoring The Phase Angle Of The Positive Sequence Power - Siemens SIPROTEC Manual

Line differential protection with distance protection
Hide thumbs Also See for SIPROTEC:
Table of Contents

Advertisement

Effect of the Measuring Voltage Failure
In the event of a measuring voltage failure due to a short-circuit or broken conductor in the voltage transformer
secondary circuit, some or all measuring loops may mistakenly see a voltage of zero. In case that load currents
exist simultaneously, incorrect pickup could occur. If such a voltage failure is detected, the protection functions
that operate on the basis of undervoltage are blocked. The O/C emergency operation is possible during the
voltage failure, provided that the O/C protection is parameterized accordingly (refer to Section 2.16).
Figure 2-210 shows the effect on the protection functions in case that a measuring voltage is detected by the
„fuse failure monitor" „VT FuseFail" (no. 170), „VT FuseFail>10s" (no. 169), the additional measuring
voltage failure monitoring „Fail U absent" (no. 168) and the binary input of the VT miniature circuit breaker
„>FAIL:Feeder VT" (no. 361).
Figure 2-210

2.24.1.4 Monitoring the Phase Angle of the Positive Sequence Power

This monitoring function allows determining the direction of power flow. You can monitor the phase angle of the
complex power, and generate an indication when the power phasor is inside a settable segment.
One example of this application is the indication of capacitive reactive power. The monitoring indication can
then be used to control the overvoltage protection function. For this purpose, two angles must be set, as shown
in Figure 2-211. In this example, ϕA = 200° and ϕB = 340° has been set.
If the measured phase angle ϕ(S
by the angles ϕA and ϕB, the indication „ϕ(PQ Pos. Seq.)" (No. 130) is output. The angles ϕA and ϕB can
be freely set in the range between 0° and 359°. The area starts at ϕA and extends in a mathematically positive
sense as far as the angle ϕB. A hysteresis of 2° is provided to prevent erroneous indications which might
emerge at the threshold limits.
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
Effect of the measuring voltage failure
) of the positive sequence power is within the area of the P-Q plane delimited
1
Functions
2.24 Monitoring Functions
429