Chapter 6 Maintenance and Troubleshooting
Upgrading the Firmware
Upgrading the IOC
Use the following procedure to upgrade a single IOC in basic configuration.
Note:
up to 30 minutes until the upgraded IOC enters the Locked
mode.
To avoid interrupting outputs in a redundant system, upgrade the standby card,
reboot, wait until it leaves warm-up, make it active, then upgrade and reboot the
other card.
1. Login at the Admin level (see
2. Type
set configuration backup local
of the IOC configuration.
3. Type
upgrade ioc1 <filepath> <ftp-server> <user name>
address of the server) and press Enter.
Note: The FTP firewall is set to "Block" by default. Use the following
command to set the IMC firewall to "Allow" for telnet communications:
Note: The TimeProvider 5000 only supports active FTP; it does not
support passive (PASV) mode.
Note: For SFTP, both the SFTP and SSH firewalls must be set to
"Allow". They are both set to "Allow" by default.
Note:
be included with the address.
Example - FTP: For an FTP server with IP address 192.168.5.64, a user name of
"user1", and an upgrade file path of "/ver2.bin" the command is:
upgrade ioc1 /ver2.bin ftp:192.168.5.64 user1
346 TimeProvider 5000 User's Guide
Outputs from the TimeProvider 5000 are interrupted for
Logging In And
set firewall imc ftp allow
If an SFTP server is used, the protocol does not need to
ftp:192.168.5.64
[sftp:]192.168.5.64
Out, on page 316).
and press Enter to save the contents
098-00028-003 Revision A – June, 2011