Section 6: DeviceNet Interface Module
May 2022
6.2
Wiring Diagram
The DeviceNet interface is connected to the actuator terminal board by internal wiring, see
Figure 20.
Figure 20
6.3
Bus/Hardwired Mode Selection
The DeviceNet interface manages the bus/hardwired mode selection by means of the
input terminal indicated with HW MODE. The physical input accepts from 24 V - 125 V DC
or AC, polarity insensitive. When the input is left unconnected or no voltage is applied,
the actuator is under bus control from which is possible to send commands and read
status. When an appropriate voltage is applied to the HW MODE input, the actuator turns
under Hardwired control. In this condition, the bus can only read actuator status while the
actuator follows the hardwired open and close controls connected to the terminal board.
For further details, please refer to Installation, Operation and Maintenance Manual for
Keystone EPI2, Electric Actuator.
14
Installation, Operation and Maintenance Manual
Optional module - DeviceNet interface
Connector H
5
6
7
8
9
CAN_H
CAN_V+
(white)
(red)
HW Mode
CAN_V-
(black)
DeviceNet line
VCIOM-02377-EN Rev. 0
17
18
19
Shield
CAN_L
(blue)
DeviceNet Interface Module