WARRANTY Parker SSD Drives warrants the goods against defects in design, materials and workmanship for the period of 24 months from the date of manufacture, or 12 months from the date of delivery (whichever is the longer period), on the terms detailed in Parker SSD Drives Standard Conditions of Sale IA500504.
Mechanical Installation NOTE Refer to the Safety and EMC sheets provided with the drive. Mount unit vertically inside a suitable cubicle. Drill mounting holes accurately. Check for material that could damage/restrict operation. • Fit 4 x inserts into the back panel •...
Electrical Installation Refer to the Safety and EMC sheets provided with the drive. NOTE An EMC compliant installation is shown. Earth/Ground Connections IMPORTANT Refer to "Permanent Earthing" on the Installation Diagram. Earth/Ground Rails Provide a (dirty) earth/ground rail (11) inside the cubicle. Connect it to an external earth/ground, PE. Provide a (clean) earth/ground rail (2) inside the cubicle, connected directly to the (dirty) earth/ground rail and insulated from the mounting panel.
Page 4
Installation Diagram * Permanent Earthing The unit must be permanently earthed Control Terminals according to EN 50178: A cross-section conductor of at least 10mm required. D5 D6 D8 D7 A+ A- D3 D4 L1 L2 L3 Power Terminals (F-) (F+) This can be achieved by using a single conductor (PE) or by laying a...
Control Connections Refer to the Installation Diagram • Control wiring must have a minimum cross-section area of 0.75mm (18AWG) • Use screened control cables to comply with EMC requirements Current Limit Connection to allow the MAIN CURR. LIMIT parameter to adjust the current limit. (fixed) Removing B8 from C9 (24V) causes a Program Stop (regenerative drive only) Removing B9 from C9 (24V) causes a Coast Stop...
D7 (N) 270A). Protect with external fuses determined by the contactor holding VA, or MCB. Supply D8 (L) Connect auxiliary supply terminals directly to the incoming supply. No series sequencing switches or contacts are permitted without consultation from Parker SSD Drives.
Drive Set-Up IMPORTANT You must not exceed the maximum drive and motor ratings. Refer to the Product Code or rating label, and the motor rating plate The instructions are written in logical order. Complete each stage successfully before progressing to the next. This simple start-up routine assumes that: •...
2: Calibrating the Control Board NO POWER IS CONNECTED AT THIS STAGE IA CAL IF CAL VA CAL Lift the hinged terminal cover to reveal the control board. X100 X0.1 Enter the settings for Armature Current, Field Current and Armature Voltage.
3: Initial Start-Up Routine AUXILIARY POWER ONLY IS CONNECTED AT THIS STAGE Complete steps 3.1 to 3.12 Write down the MAIN CURR. 3.2 Check that ANIN 5 (A6) is LIMIT parameter’s value +10V. If not, check the here: wiring link between terminals A6 and B3.
Page 10
ISOLATE THE DRIVE using branch circuit protection or circuit breaker (8). Install the 3-phase fuses (6). Re-instate branch circuit protection or circuit breaker (8) IMPORTANT Do not change any of the previously made calibration settings once the main contactor is energised. MAIN &...
Caution During the following set-up instructions, be ready to STOP the drive should the motor try to overspeed. Set the speed potentiometer to 5% (0.5V at terminal A8). Refer back to 3.1 to display the CONFIGURE DRIVE menu. Slowly increase the MAIN CURR.LIMIT parameter towards a maximum of 20%.
Page 12
In the Product Manual refer to the sections below to make the installation application specific: CHAPTER 3 Connection Diagrams Control Connections Optional Equipment CHAPTER 4 Selecting Speed Feedback Initial Start-up Routine (the full routine will help with any additions you make) Performance Adjustment (any parameter changes will require another Autotune) www.parker.com...
0 : ARM VOLTS FBK 1 : ANALOG TACH 2 : ENCODER 3 : ENCODER/ANALOG – for Parker SSD Drives use Refer to SPEED LOOP ENCODER LINES 10 to 5000 The number of lines must be set to match the type of encoder being used.
Electrical Ratings - Power Circuit Output Current @ 100% Power @ 460V dc Field Current Approximate Total Losses Max Supply Fault Current Continuous * (kW) @ Full Load rms symmetrical (kA) * The standard overload capacity available is 200% for 10 seconds, 150% for 30 seconds. Power Supply Details 3-Phase Supply 3-phase, 50/60Hz, earth referenced (TN) and non-earth referenced (IT)