Connection Device Information

Set the information of the connected device.
Item
Description
CC-Link IE TSN
Set the CC-Link IE TSN Class of the connected device.
Class Settings
TSN HUB Setting
Set whether to use a TSN hub or not when using a structure of mixed CC-Link IE TSN
Class B devices and CC-Link IE TSN Class A devices.
Set "Use TSN HUB" when connecting a TSN hub.
Precautions
• For a structure with mixed CC-Link IE TSN Class B devices and CC-Link IE TSN Class A devices, set "TSN HUB Setting"
to "Use TSN HUB" when connecting a TSN hub.
• When "Network Topology" is set to "Ring", set "CC-Link IE TSN Class Setting" of "Connection Device Information" to "CC-
Link IE TSN Class B Only". If "Mixture of CC-Link IE TSN Class B/A or CC-Link IE TSN Class A Only" is set, an error code
(3016H) is output.
• When "TSN HUB Setting" is set to "Not to Use TSN HUB" and a TSN hub is connected, the slave station may not perform
data link. ( Page 201 CC-Link IE TSN Class A device does not perform data link)

Slave Station Setting

Set items related to the slave station.
Item
Description
Disconnection
Set the number of consecutive communication failures until a slave station is considered disconnected.
Detection
Setting

Safety Communication Setting

Set whether to use the safety communication or not and set safety connections.
Item
To Use or Not to Use the Safety
Communication Setting
Safety Communication Setting
Set the following items before configuring the safety communication setting.
• "Network Configuration Settings" in "Basic Settings" ( Page 117 "CC-Link IE TSN Configuration"
Window)
If the above items are not set, the slave station is not displayed as the target module in the "Select the target
module for the Safety Communication Setting" window and safety communications cannot be set.
2 PARAMETER SETTINGS
104
2.3 Basic Settings
Description
Set whether to use the safety communication or not.
Set the safety connections and transfer ranges of safety devices required for safety
communications.
Setting range
• CC-Link IE TSN Class B Only
• Mixture of CC-Link IE TSN Class B/A or
CC-Link IE TSN Class A Only
(Default: CC-Link IE TSN Class B Only)
• Not to Use TSN HUB
• Use TSN HUB
(Default: Not to Use TSN HUB)
Setting range
• 2 times
• 4 times
• 8 times
(Default: 4 times)
Setting range
• Not Use
• Use
(Default: Not Use)
Page 105 Setting method