Label
PARAMETER_NAME
Manufacturer Id
MANUFAC_ID
Device Type
DEV_TYPE
Device Revision
DEV_REV
DD Revision
DD_REV
Grant Deny
GRANT_DENY
GRANT
DENY
Hard Types
HARD_TYPES
Restart
RESTART
Features
FEATURES
Features Selected
FEATURE_SEL
December 2009
Table 4-3. Resource Block Parameter Definitions (Continued)
Index
RO /
Mode
Number
RW
10
RO
N/A
11
RO
N/A
12
RO
N/A
13
RO
N/A
14
14.1
RW
ALL
Valid Bits:
0: Program
1: Tune
2: Alarm
3: Local
14.2
RW
ALL
0: Scalar Input
1: Scalar Output
15
RO
N/A
2: Discrete Input
3: Discrete Output
1=Run
2=Restart resource
16
RW
ALL
3=Restart with
defaults
4=Restart processor
1: Reports supported
2: Fault State
supported
17
RO
ALL
3: Software Write
lock supported
10: Reannunciation
supported
1: Reports Supported
2: Fault State
supported
18
RW
ALL
3: Software Write
lock supported
10:Reannunciation
supported
−Continued−
Resource Block
Initial
Range
Value
Data Type: Unsigned32
Manufacturer identification number, used by an
interface device or host to locate the DD file for
the resource. All manufacturer identification
numbers are maintained by the Fieldbus
Foundation. A host usually will have a base
directory for DD files. In this directory is a
0x5100
subdirectory for each manufacturer id. In each
manufacturer id subdirectory is a directory for
each device type made by that manufacturer.
The device type directories contain files named
by combining the device revision for the
particular device type with the revision of the
device description. The manufacturer id for
Fisher is 0x005100.
Data Type: Unsigned16
Manufacturer's model number associated with
4602
the resource, used by an interface device to
locate the DD file for the resource.
Data Type: Unsigned8
Manufacturer's revision number associated
Varies with
release
with the resource, used by an interface device
to locate the DD file for the resource.
Data Type: Unsigned8
The minimum revision of the device description
Varies with
(DD) than can be used with the device revision
release
of the instrument. Used by the interface device
to prevent the use of DDs that are incompatible
with the firmware in the instrument.
Data Type: DS-70
Options for controlling access of a host
All bits: 0
computer and to block parameters. Parameter
contains two attributes Grant and Deny each
with program, tune, alarm and local
permissions. Clearing a grant permission sets
the corresponding deny permission, 0 = N/A, 1
= granted.
All bits: 0
Deny permissions may be cleared through the
Deny attribute but not set, 0 = N/A, 1 = denied.
Data Type: Bit String
0: 1
0 = Inactive
1: 1
1 = Active
2: 1
The types of hardware available as channel
3: 1
numbers in this resource.
Data Type: Unsigned8
Allows a manual restart to be initiated. For
1=Run
details see Restarting the Instrument in this
section.
Data Type: Bit String
1: 1
0 = Inactive
2: 1
1 = Active
3: 1
Shows the supported resource block options.
10: 1
Options are turned on and off via
FEATURE_SELECT.
Data Type: Bit String
1:0
0 = Inactive
2:1
1 = Active
3:1
Shows the selected resource block options.
10:0
For details see Device Features in this section.
Description
4
4-13