Label
PARAMETER_NAME
INST_ALERTS_CONFIG2
Travel Deviation Alert Point
TVL_DEV_ALRT_PT
Travel Deviation Time
TVL_DEV_TIME
Travel Deviation Deadband
TVL_DEV_DB
Travel Accumulator Alert Point
TVL_ACCUM_ALRT_PT
Travel Accumulator Deadband
TVL_ACCUM_DB
Cycle Count Alert Point
CYCLE_COUNT_ALRT_PT
Cycle Count Deadband
CYCLE_COUNT_DB
Travel Open Alert Point
TVL_OPEN_ALRT_PT
Travel Open Deadband
TVL_OPEN_DB
Travel Closed Alert Point
TVL_CLOSED_ALRT_PT
Travel Closed Deadband
TVL_CLOSED_DB
Travel Lo Lo Alert Point
TVL_LO_LO_ALRT_PT
Travel Lo Lo Deadband
TVL_LO_LO_DB
Travel Lo Alert Point
TVL_LO_ALRT_PT
Travel Lo Deadband
TVL_LO_DB
Travel Hi Alert Point
TVL_HI_ALRT_PT
Travel Hi Deadband
TVL_HI_DB
Travel Hi Hi Alert Point
TVL_HI_HI_ALRT_PT
Travel Hi Hi Deadband
TVL_HI_HI_DB
December 2009
Table 4-13. Transducer Block Parameter Definitions (Continued)
Index
RO /
Mode
Range
Number
RW
77
> 0%, <= 125%
77.1
RW
ALL
> = 0, < = 120 seconds
77.2
RW
ALL
> = 0%, < = 100%
77.3
RW
ALL
> = 0
77.4
RW
ALL
0 − 100%
77.5
RW
ALL
> = 0
77.6
RW
ALL
0 − 100%
77.7
RW
ALL
−25% to 125%
77.8
RW
ALL
> = 0%, < =100%
77.9
RW
ALL
−25% to 125%
77.10
RW
ALL
> = 0%, < = 100%
77.11
RW
ALL
−25% to 125%
77.12
RW
ALL
> = 0%, < = 100%
77.13
RW
ALL
−25% to 125%
77.14
RW
ALL
> = 0%, < = 100%
77.15
RW
ALL
−25% to 125%
77.16
RW
ALL
> = 0%, < = 100%
77.17
RW
ALL
−25% to 125%
77.18
RW
ALL
> = 0%, < = 100%
77.19
RW
ALL
−Continued−
Transducer Block
Protect
Initial Value
Category
Data Type: Float
Alerts when difference between sp
5%
SETUP
and pv is too large for too long.
10 sec
SETUP
Data Type: Float
2%
SETUP
Data Type: Float
Data Type: Uint32
1,000,000
SETUP
Alerts when accumulated travel is
too much
Data Type: Float
1%
SETUP
Deadband
Alerts when number of cycles is too
1,000,000
SETUP
large.
Data Type: Float
1%
SETUP
Deadband
Data Type: Float
Alert when valve is open. Control
99.5%
SETUP
DI channel 24 regardless of alert
enable state.
Data Type: Float
1%
SETUP
Deadband
Data Type: Float
Alerts when valve closed. Controls
0.5%
SETUP
DI channel 25 regardless of alert
enable state.
Data Type: Float
1%
SETUP
Deadband
Data Type: Float
Alert when valve position is less
−25%
SETUP
than alert point. Controls DI
channels 26 & 30 regardless of
alert enable state.
Data Type: Float
5%
SETUP
Deadband
Data Type: Float
Alert when valve position is less
−25%
SETUP
than alert point. Controls DI
channels 27 & 31 regardless of
alert enable state.
Data Type: Float
5%
SETUP
Deadband
Data Type: Float
Alert when valve position is less
125%
SETUP
than alert point. Controls DI
channels 28 & 32 regardless of
alert enable state.
Data Type: Float
5%
SETUP
Deadband
Data Type: Float
Alert when valve position is less
than alert point. Controls DI
125%
SETUP
channels 29 & 33 regardless of
alert enable state.
Data Type: Float
5%
SETUP
Deadband
Description
4
4-59

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Fisher FIELDVUE DVC6000f and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents