Label
PARAMETER_NAME
TRAVEL
Travel Status
STATUS
Travel
VALUE
SUPPLY_PRESSURE
Supply Pressure Status
STATUS
Supply Pressure
VALUE
PRESSURE_A
Pressure A Status
STATUS
Pressure A
VALUE
PRESSURE_B
Pressure B Status
STATUS
Pressure B
VALUE
PRESSURE_DIFF
Pressure Differential Status
STATUS
Pressure Differential
VALUE
PWA Simulate
PWA_SIMULATE
Grant Deny
GRANT_DENY
GRANT
DENY
Travel Pressure Control
TVL_PRESS_CONTROL
Travel/Pressure Select
TVL_PRESS_SELECT
Travel/Pressure State
TVL_PRESS_STATE
December 2009
Table 4-13. Transducer Block Parameter Definitions (Continued)
Index
RO /
Mode
Range
Number
RW
34
34.1
RO
N/A
34.2
RO
N/A
35
35.1
RO
N/A
35.2
RO
N/A
36
36.1
RO
N/A
36.2
RO
N/A
37
37.1
RO
N/A
37.2
RO
N/A
38
38.1
RO
N/A
38.2
RO
N/A
RO
1=Simulate Off
39
or
ALL
2=Simulate Enabled
RW*
40
40.1
RW
ALL
0: Program
1: Tune
2: Alarm
3: Local
40.2
RW
ALL
41
1=Travel
2=Pressure
3=TVL/PRESS Auto
41.1
RW
ALL
Recv
4=TVL/PRESS Man
Recv
1=Travel
41.2
RO
N/A
2=Pressure
−Continued−
Transducer Block
Protect
Initial Value
Category
Data Type: DS-65
In Travel Control: Actual valve
travel in % of calibrated travel
N/A
range.
In Pressure Control: Implied valve
travel in % of pressure range.
N/A
Controls AI channel 4.
Data Type: DS-65
STATUS indicates the validity of
N/A
VALUE. VALUE is pressure of air
supply, controls AI channel 5.
N/A
Data Type: DS-65
STATUS Indicates the validity of
N/A
VALUE.
Pressure of primary air output,
controls AI channel 6.
N/A
Data Type: DS-65
STATUS indicates the validity of
N/A
VALUE. VALUE is the
Pressure on secondary output,
controls AI channel 7.
N/A
Data Type: DS-65
STATUS indicates the validity of
VALUE. VALUE is the difference
N/A
between PRESSURE_A and
PRESSURE_B, controls AI channel
N/A
8.
Data Type: Enum (Uint8)
When this is set to 2 all the alert
ACTIVE parameters can be written,
except for INST_ALERTS_ACTIVE.
SHUTDOWN_ALERT_ACTIVE.
This allows alerts to be simulated
1=Simulate Off
ALL
for testing with hosts. NOTE: only
ACTIVE parameters are affected by
this. * PWA Simulate is RW only if a
jumper is installed across the Aux
Terminal. If no jumpered is installed
across the Aux Terminal, PWA
Simulate is RO.
Data Type: DS-50
Options for controlling access of
all bits cleared
NONE
host computer and local control
panels to operating, tuning, and
alarm parameters of the block. Has
no effect on the DVC6000f.
all bits cleared
NONE
GRANT: 0=N/A, 1= granted
DENY: 0=N/A, 1= denied
Data Type: Enum (Uint8)
Selects whether travel sensor or
1=Travel
SETUP
port A pressure is used for
feedback.
Data Type: Enum (Uint8)
N/A
Indicates which sensor is used for
feedback
Description