DVC6000f Digital Valve Controllers
Block Errors
Table 4-61 lists conditions reported in the
BLOCK_ERR [6] parameter. Conditions in italics are
inactive for the MAI block and are given here only for
your reference.
Table 4-61. BLOCK_ERR Conditions
Condition
Condition Name and Description
Number
0
Other
Block Configuration Error: the selected channel carries
a measurement that is incompatible with the engineering
1
units selected in XD_SCALE, the L_TYPE parameter is
not configured, or WRITE_CHECK = 0.
4
2
Link Configuration Error
3
Simulate Active
4
Local Override
5
Device Fault State
6
Device Needs Maintenance Soon
Input failure/process variable had Bad status - The
7
hardware is bad, or a bad status is being simulated
8
Output failure
9
Memory failure
10
Lost Static Data
11
Lost NV Data
12
Readback Check Failed
13
Device Needs Maintenance Now
Power Up − This condition exists after power up until the
14
MAI funciton executes for the first time.
15
Out of Service - The actual mode is Out of Service.
4-142
Troubleshooting
Refer to table 4-62 to troubleshoot any problem that
you encounter.
Table 4-62. Troubleshooting
Symptom
Possible Causes
Mode will not leave
Target mode is not
OOS
set
Resource block
Schedule
Block alarms will
not work
Features
Notification
Corrective Action
Set target mode to
something other than OOS
The actual mode of the
Resource block is OOS.
See Resource Block
Diagnostics for corrective
action.
Block is not scheduled and
therefore cannot execute to
go to Target Mode.
Typically, BLOCK_ERR [6]
will show "Power-Up" for all
blocks that are not
scheduled. Schedule the
block to execute.
FEATURES_SEL [18] in
the resource block does
not have Alerts enabled.
Enable the Alerts bit.
LIM_NOTIFY [32] in the
resource block is not high
enough. Set equal to
MAX_NOTIFY [31], also in
the resource block.