Block Errors
Table 4-12 lists conditions reported in the
BLOCK_ERR [6] and XD_ERR [11] parameters.
Conditions in italics are not applicable for the
transducer block and are provided only for your
reference.
Table 4-12. Transducer Block BLOCK_ERR and
XD_ERROR Conditions
Condition
Condition Name and Description
Number
0
Other - (N/A)
Block Configuration Error - Indicates that one of the
1
following parameters have been configured out of the
proper range: 15, 16, 47.1, 47.2, 46.3, 46.5, 42.7, 42.8.
2
Link Configuration Error - (N/A)
Simulate Active - Indicates that the simulation jumper is
in place on the aux terminals. This is not an indication
3
that the I/O blocks are using simulation data. See AO
block parameter SIMULATE [10] and DO block parameter
SIMULATE_D [10].
4
Local Override - (N/A)
Device Fault State − (NA)
5
6
Maintenance Needed Soon - (N/A)
7
Input failure/process variable has Bad status - (N/A)
8
Output failure - (N/A)
9
Memory failure - (N/A)
Lost Static Data - Indicates that manufacturing functional
10
or thermal tests were incomplete
11
Lost NV Data - (N/A)
12
Readback Check Failed - (N/A)
Device Needs Maintenance Now - Indicates that
13
manufacturing functional or thermal tests were incomplete
14
Power Up - (N/A)
15
Out of Service - Indicates Out of Service Mode.
December 2009
Transducer Block
4
4-41