Label
PARAMETER_NAME
PRESS_CAL
Supply Pressure Scale
SUPP_PRESS_SCALE
Supply Pressure Offset
SUPP_PRESS_OFFSET
Pressure A Scale
PRESS_A_SCALE
Pressure A Offset
PRESS_A_OFFSET
Pressure B Scale
PRESS_B_SCALE
Pressure B Offset
PRESS_B_OFFSET
Pressure IP Bias
PRESS_IP_BIAS
Pressure MLFB Bias
PRESS_MLFB_BIAS
PRESS_TUNE
Pressure Cutoff Hi
PRESS_CUTOFF_HI
Pressure Cutoff Lo
PRESS_CUTOFF_LO
Pressure Proportional Gain
PRESS_PROP_GAIN
Pressure Integral Gain
PRESS_INTEG_GAIN
Pressure Rate Gain
PRESS_RATE_GAIN
Pressure Integral Dead Zone
PRESS_INTEG_DEADZ
Pressure Integral Limit Hi
PRESS_INTEG_HI_LIM
Pressure Integral Limit LO
PRESS_INTEG_LO_LIM
Pressure Integral IC Hi
PRESS_INTEG_IC_HI
Pressure Integral IC Lo
PRESS_INTEG_IC_LO
Pressure MLFB Gain
PRESS_MLFB_GAIN
Temperature
TEMPERATURE
Target Travel
TRAVEL_TARGET
Status
STATUS
Value
VALUE
Input Characterization
INPUT_CHAR
December 2009
Table 4-13. Transducer Block Parameter Definitions (Continued)
Index
RO /
Mode
Range
Number
RW
46
MAN
> 0
46.1
RW
OOS
MAN
46.2
RW
0 to 16383
OOS
MAN
> 0
46.3
RW
OOS
MAN
46.4
RW
0 to 16383
OOS
MAN
> 0
46.5
RW
OOS
MAN
46.6
RW
0 to 16383
OOS
MAN
46.7
RW
0−100%
OOS
MAN
46.8
RW
0−100%
OOS
47
−25 −125%,
MAN
47.1
RW
> CUTOFF_LO
OOS
−25 −125% <
MAN
47.2
RW
OOS
CUTOFF_HI
MAN
> = 0, < 32
47.3
RW
OOS
MAN
> = 0, < 32
47.4
RW
OOS
MAN
> = 0, < = 512
47.5
RW
OOS
MAN
< = 2.0%
47.6
RW
= 0%,
OOS
> = 0%, < = 100%,
MAN
47.7
RW
>INTEG_LO
OOS
< = 0%, > = −100%,
MAN
47.8
RW
<INTEG_HI
OOS
MAN
>= −100%, < = 100%
47.9
RW
OOS
MAN
>= −100%, < = 100%
47.10
RW
OOS
MAN
> 0, < = 100
47.11
RW
OOS
48
RO
N/A
49
RO
MAN
49.1
RO
OOS
MAN
49.2
RO
OOS
1=Linear
2=Equal %
MAN
50
RW
3=Quick Opening
OOS
4=Reserved
5=Custom
−Continued−
Transducer Block
Protect
Initial Value
Category
CAL
Data Type: Float
CAL
Data Type: Uint16
CAL
Data Type: Float
CAL
Data Type: Uint16
CAL
Data Type: Float
CAL
Data Type: Uint16
70%
CAL
Data Type: Float
50%
CAL
Data Type: Float
99.50%
SETUP
Data Type: Float
0.50%
SETUP
Data Type: Float
Data Type: Float
2.2
SETUP
Proportional gain
Data Type: Float
0.1
SETUP
Integral resets per second
Data Type: Float
0
SETUP
Derivative gain
Data Type: Float
0.25%
SETUP
Integrator Deadzone, 1/2 width
Data Type: Float
20%
SETUP
Integrator limits
Data Type: Float
−20%
SETUP
Integrator limits
12%
Not used by the DVC6000f
−12%
Not used by the DVC6000f
35
SETUP
Data Type: Float
Data Type: Float
Electronics temperature − Controls
N/A
N/A
AI channel 11
Data Type: DS-65
In Travel Control: Setpoint for valve
N/A
travel in %, post characterization.
In Pressure Control: Setpoint for
implied valve travel as a % or
N/A
pressure range, post
characterization.
1=Linear
SETUP
Data Type: Enum (Uint8)
Description
4
4-49