AO Block Parameter List
D Read/Write Capability: RO − Read Only, RW − Read Write
D Mode: The block mode(s) required to write to the parameter
D Double indentation and shaded Index Number indicates sub-parameter
Label
PARAMETER_NAME
Static Revision
ST_REV
Tag Description
TAG_DESC
Strategy
STRATEGY
Alert Key
ALERT_KEY
Block Mode
MODE_BLK
TARGET
ACTUAL
PERMITTED
NORMAL
Block Error
BLOCK_ERR
Process Variable
PV
Set Point
SP
Output
OUT
December 2009
Table 4-24. Analog Output Function Block Parameter Definitions
Index
RO /
Block
Number
RW
Mode
1
RO
N/A
0 to 65535
2
RW
ALL
7 bit ASCII
3
RW
ALL
0 to 65535
4
RW
ALL
1 to 255
5
OOS
MAN
AUTO
5.1
RW
ALL
AUTO-CAS
AUTO-RCAS
5.2
RO
ALL
OOS+MAN+AUTO+
5.3
RW
ALL
CAS+RCAS
5.4
RW
ALL
1: Block Configuration
Error
3: Simulate Active
4: Local Override
6
RO
N/A
5: Device Fault State
Set
8: Output Failure
14: Power-up
15: Out-of-Service
PV Status set equal
7
RO
N/A
to READBACK status
OOS
MAN
8
PV_SCALE +/− 10%
AUTO
MAN
9
OUT_SCALE +/− 10%
OOS
AO Function Block
Initial
Range
Value
Data Type: Unsigned16
The revision level of the static data associated
0
with the function block. The revision value will be
incremented each time a static parameter value in
the block is changed.
Data Type: Octet String
Spaces
The user description of the intended application of
the block.
Data Type: Unsigned16
The strategy field can be used to identify grouping
0
of blocks. This data is not checked or processed
by the block.
Data Type: Unsigned8
The identification number of the plant unit. This
0
information may be used in the host for sorting
alarms, etc.
OOS until
Data Type: DS-69
block is
Valid Bits: 7: OOS, 6: IMAN, 5: LO, 4: MAN, 3:
configured,
AUTO, 2: CAS, 1: RCAS
then last valid
The actual, target, permitted, and normal modes
target
of the block.
OOS
OOS+MAN+
AUTO+
CAS+RCAS
AUTO
Data Type: Bit String (2 byte)
0=inactive
1=active
This parameter reflects the error status
Dynamic
associated with the hardware or software
components associated with a block. It is a bit
string, so that multiple errors may be shown. See
table 4-23.
Data Type: DS-65
The process variable used in block execution.
This value is converted from READBACK to show
Dynamic
the actuator position in the same units as the
setpoint value.
Data Type: DS-65
The SP of the analog block. Can be derived from
CAS_IN, RCAS_IN in normal modes, or can track
Dynamic
PV in MAN, IMan or LO modes. IO_OPTS is used
to determine value of SP in MAN, IMan or LO. If
no IO_OPTS for SP tracking are set, SP will
freeze when mode changes from CAS or RCAS.
Data Type: DS-65
The primary value and status calculated by the
Dynamic
block in Auto mode. OUT may be set manually in
Man mode.
−Continued−
Description
Target: The requested block mode
Actual: The current mode of the block
(Note: Bit 6 (IMAN) is valid for ACTUAL only)
Permitted: Allowed modes for Target
Normal: Most common mode for Target
4
4-75