Label
PARAMETER_NAME
Block Alarm
BLOCK_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
Transducer Directory
TRANSDUCER_DIRECTORY
Transducer Type
TRANSDUCER_TYPE
Transducer Error
XD_ERROR or TDC_ERROR
Collection Directory
COLLECTION_DIRECTORY
FINAL_VALUE
Setpoint Status
STATUS
Setpoint
VALUE
Setpoint Range
FINAL_VALUE_RANGE
EU_100
EU_0
UNITS_INDEX
DECIMAL
Travel Cutoff Hi
FINAL_VALUE_CUTOFF_HI
Travel Cutoff Lo
FINAL_VALUE_CUTOFF_LO
December 2009
Table 4-13. Transducer Block Parameter Definitions (Continued)
Index
RO /
Mode
Range
Number
RW
8
0=Undefined
8.1
RW
ALL
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clear−reported
2=Clear−not reported
8.2
RO
N/A
3=Active−reported
4=Active−not reported
8.3
RO
N/A
Subcode: Bit Number in
8.4
RO
N/A
BLOCK_ERR
Value of parameter at
alarm time for a single
8.5
RO
N/A
alarm, 0 for multiple
alarms
9
RO
N/A
1,1
10
RO
106
Valid Numbers: 0 = No
11
RO
Error
12
RO
1,1,1,1,1
13
MAN
13.1
RW
OOS
MAN
−25 to 125
13.2
RW
OOS
14
14.1
RO
N/A
100
14.2
RO
N/A
0
14.3
RO
N/A
PERCENT
14.4
RO
N/A
2
MAN
−25 to 125
15
RW
OOS
MAN
−25 to 125
16
RW
OOS
−Continued−
Transducer Block
Protect
Initial Value
Category
0
NONE
0
N/A
Data Type: DS-72
Used to report the BLOCK_ERR
0
N/A
alarm to the host system
0
N/A
0
N/A
Data Type: Array [2] of Unit16
1,1
N/A
Not used
Data Type: Uint16
106
N/A
Identifies the type of the transducer.
Data Type: Uint8
0
N/A
Error code for the transducer block.
Data Type: Array [5] of Unit32
1,1,1,1,1
N/A
Not used
Data Type: DS-65
In Travel Control: Setpoint for valve
travel in %, prior to
N/A
NONE
characterization.
In Pressure Control: Setpoint for
implied valve travel as % or
pressure range, prior to
characterization.
FINAL_VALUE is not updated
unless the AO block is selected in
N/A
NONE
FEATURE_SELECT. For example,
FINAL_VALUE still has last value
written by AO channel 1 when DO
is in control.
Data Type: DS-68
High and Low range limit values,
100
N/A
engineering units code, and
0
N/A
number of digits to the right of the
decimal place to be used to display
1342
N/A
the Final Value.
2
N/A
Data Type: Float
When the servo goes above this %
of span, the stem position goes to
99.5
SETUP
the upper limit. Cutoffs are OFF
when Low is at −25% and high is at
+125%. Must be > low cutoff +
.625%.
Data Type: Float
When the servo goes below this %
of span, the stem position goes to
0.5
SETUP
the lower limit. Cutoffs are OFF
when Low is at −25% and high is at
+125%. Must be < hi cutoff −
.625%.
Description
4
4-43