DVC6000f Digital Valve Controllers
Label
PARAMETER_NAME
Advise Active
ADVISE_ACTIVE
4
Failed Enable
FAILED_ENABLE
Maintenance Enable
MAINT_ENABLE
Advise Enable
ADVISE_ENABLE
Failed Suppress
FAILED_MASK
1. These parameters can be written when PWA_SIMULATE is active and Protect Category is not ALL.
4-52
Table 4-13. Transducer Block Parameter Definitions (Continued)
Index
RO /
Mode
Range
Number
RW
0: Drive Current
1: Drive Signal
2: Processor Impaired
3: Output Block Timeout
4: Blocks Set to Defaults
5: Travel Sensor
6: Outlet Pressure
Sensor
7: Supply Pressure
Sensor
8: Temperature Sensor
(1)
61
RO
N/A
9: Supply Pressure
10: Temperature Limit
11: Travel Deviation
12: Travel Limit
13: Travel Accumulator
14: Cycle Counter
15: Performance Critical
16: Performance
Reduced
17: Performance
Information
18: Shutdown Alert
Same as for
62
RW
ALL
FAILED_ACTIVE above
Same as for
63
RW
ALL
MAINT_ACTIVE above
Same as for
64
RW
ALL
ADVISE_ENABLE above
Same as for
65
RW
ALL
FAILED_ACTIVE above
−Continued−
Protect
Initial Value
Category
Data Type: Bit String (4 byte)
0=inactive
All bits: 0
N/A
1=active
Advise Alert Status
Enabled Bits:
0: Drive Current
2: Processor
Data Type: Bit String (4 byte)
Impaired
0=disable
4: Blocks Set to
1=enable
Default
ALL
Failed alert enable. Enable allows
5: Travel Sensor
detection of alert. All alerts can be
15: Performance
disabled.
Critical
18: Shutdown
Alert
Enabled Bits:
1: Drive Signal
3: Output Block
Timeout
6: Outlet Pressure
Data Type: Bit String (4 byte)
Sensor
0=disable
9: Supply
1=enable
Pressure
ALL
Maintenance alert enable. Enable
11: Travel
allows detection of alert. All alerts
Deviation
can be disabled.
13: Travel
Accumulator
14: Cycle Counter
16: Performance
Reduced
Enabled Bits:
8: Temperature
Data Type: Bit String (4 byte)
Sensor
0=disable
9: Supply
1=enable
ALL
Pressure Sensor
Advise alert enable. Enable allows
10: Temperature
detection of alert. All alerts can be
Limit
disabled.
12: Travel Limit
Data Type: Bit String (4 byte)
0=disable
1=enable
Failed alert mask. MASK controls
whether an alert is reported. If alert
All bits: 0
ALL
is enabled the alert condition is
evaluated and the ACTIVE
parameter is updated to reflect if
alert is active or not. If the bit is set
reporting is suppressed. Default is
all bits cleared.
Description