Chapter 2 Installing the SSU-2000e

Installing the SDU-2000e

ICS command:
Type
CONFIG 1A3 REMOVE
TL1 command:
RMV-MODULE::S1A3:123;
9. Verify that the module is not in the registry:
ICS command:
Type
CONFIG
TL1 command:
RTRV-INV:::123;
Installing the SDU-2000e
This section provides guidelines and procedures for installing and cabling the
SDU-2000e expansion chassis to the SSU-2000e main chassis. Before proceeding
with the SDU-2000e installation, ensure that the procedures in
Procedures, on page 58, have been performed.
The SDU-2000e chassis occupies 500 mm of vertical space, has a depth of 229
mm, and a width of 431.8 mm. Included are 530 mm ETSI compatible rack
mounting ears. Optional 480 mm rack mounting ears are available for 480 mm EIA
racks and cabinets. The SDU-2000e may be mounted on either a standard ETSI
mounting rack or 300 mm deep equipment cabinet.
Caution: To avoid excessive heat build-up resulting in equipment
damage, ensure that there is at least 76 mm (2 RU) of free space
below the chassis.
Rack Mounting the SDU-2000e
The front panel of the chassis mounts flush to the rack or at distances of 100.5 mm
from the front of the rack. An SDU-2000e equipment cabinet mounting diagram is
shown in
Figure
1. Determine and locate the appropriate mounting brackets to be used.
2. Attach a mounting bracket to each side of the chassis by aligning two columns
(three holes per column) of the bracket with the holes on the side of the chassis.
Use the appropriate screws to attach the mounting bracket. Ensure that both
brackets are attached at equal distances from the front of the unit.
3. Mount the chassis to the front of the rack rails using the appropriate number of
screws and washers for the rack.
78
SSU-2000e User's Guide
, then press Enter.
, then press Enter.
2-13. To install the SDU-2000e in the rack, perform the following:
Preliminary
12713140-002-2 Revision E – October 2006