Endress+Hauser Proline Promag 50 Brief Operating Instructions

Endress+Hauser Proline Promag 50 Brief Operating Instructions

Electromagnetic flow measuring system
Hide thumbs Also See for Proline Promag 50:

Advertisement

Quick Links

r Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction
Q-Pulse Id VM454
Q-Pulse Id
Brief Operating Instructions
Proline Promag 50
Electromagnetic Flow Measuring System
6
8
These Brief Operating Instructions are not intended to replace the
Operating Instructions provided in the scope of supply.
Detailed information is provided in the Operating Instructions and
the additional documentation on the CD-ROM supplied.
The complete device documentation consists of:
• These Brief Operating Instructions
• Depending on the device version:
– Operating Instructions and the Description of Device Functions
– Approvals and safety certificates
– Special safety instructions in accordance with the approvals for
the device (e.g. explosion protection, pressure equipment
directive etc.)
– Additional device-specific information
KA00026D/06/EN/14.11
71154524
Active 30/09/2014
Active 30/09/2014
Page 1 of 52
Page 1 of 52

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Proline Promag 50

  • Page 1 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Brief Operating Instructions Proline Promag 50 Electromagnetic Flow Measuring System These Brief Operating Instructions are not intended to replace the Operating Instructions provided in the scope of supply.
  • Page 2: Table Of Contents

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Table of contents 1 Safety instructions ........3 1.1 Designated use .
  • Page 3: Safety Instructions

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Safety instructions Safety instructions Designated use • The measuring device is to be used only for measuring the flow of conductive liquids in closed pipes.
  • Page 4 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Safety instructions Proline Promag 50 • All parts of the device must be included in the potential equalization of the system. • Cables, certified cable glands and certified dummy plugs must be suitable to withstand the prevailing operating conditions, such as the temperature range of the process.
  • Page 5: Safety Conventions

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Safety instructions Safety conventions Warning! "Warning" indicates an action or procedure which, if not performed correctly, can result in injury or a safety hazard.
  • Page 6: Installation

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Installation Proline Promag 50 Installation Transporting to the measuring point • Transport the measuring device to the measuring point in the original packaging.
  • Page 7: Installation Conditions

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Installation Installation conditions 2.2.1 Dimensions For the dimensions of the measuring device, see the associated Technical Information on the CD-ROM.
  • Page 8 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Installation Proline Promag 50 Partially filled pipes Partially filled pipes with gradients necessitate a drain-type configuration. The empty pipe detection (EPD) function offers additional protection by detecting empty or partially filled pipes.
  • Page 9 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Installation 2.2.3 Orientation An optimum orientation helps avoid gas and air accumulations and buildup in the measuring tube. The measuring device, nevertheless, supplies a range of functions and tools to measure problematic fluids correctly: •...
  • Page 10 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Installation Proline Promag 50 Inlet and outlet runs If possible, install the sensor upstream from fittings such as valves, T-pieces, elbows, etc. The following inlet and outlet runs must be observed in ³...
  • Page 11 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Installation 2.2.5 Foundations, supports If the nominal diameter is DN ≥ 350 (≥ 14"), mount the sensor on a foundation of adequate load-bearing strength.
  • Page 12: Installing The Promag L Sensor

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Installation Proline Promag 50 Installing the Promag L sensor " Caution! • The protective covers mounted on the two sensor flanges (DN 50…300) are used to hold the lap joint flanges in place and to protect the PTFE liner during transportation.
  • Page 13 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Installation 2.3.3 Screw tightening torques (Promag L) Please note the following: • The tightening torques listed below are for lubricated threads only.
  • Page 14 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Installation Proline Promag 50 Nominal EN (DIN) Max. tightening torque diameter Hard rubber Polyurethane PTFE [mm] Pressure Threaded [Nm] [Nm] [Nm] rating [bar]...
  • Page 15 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Installation Promag L tightening torques for AWWA Nominal AWWA Threaded Max. tightening torque diameter fasteners Pressure rating Hartgummi Polyurethane PTFE...
  • Page 16 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Installation Proline Promag 50 Promag L tightening torques for AS 4087 Nominal AS 4087 Threaded Max. tightening torque diameter fasteners Pressure rating Hard rubber...
  • Page 17: Installing The W Sensor

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Installation Installing the W sensor Note! Screws, nuts, seals, etc. are not included in the scope of supply and must be supplied by the customer.
  • Page 18 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Installation Proline Promag 50 2.4.3 Screw tightening torques (Promag W) Please note the following: • The tightening torques listed below are for lubricated threads only.
  • Page 19 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Installation Nominal diameter EN (DIN) Threaded fasteners Max. tightening torque [Nm] [mm] Pressure rating [bar] Hard rubber Polyurethane PN 16 20 ×...
  • Page 20 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Installation Proline Promag 50 Promag W tightening torques for ANSI Nominal diameter ANSI Threaded fasteners Max. tightening torque Hard rubber Polyurethane Pressure rating...
  • Page 21 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Installation Nominal diameter Threaded fasteners Max. tightening torque [Nm] [mm] Pressure rating Hard rubber Polyurethane 8 × M 20 8 × M 20 8 ×...
  • Page 22 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Installation Proline Promag 50 Nominal diameter AS 2129 Threaded Max. tightening torque [Nm] [mm] Pressure rating fasteners Hard rubber Table E 12 × M 24 Table E 12 ×...
  • Page 23: Installing The Promag P Sensor

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Installation Installing the Promag P sensor " Caution! • The plates mounted on the two sensor flanges protect the PTFE which is turned over the flanges and, consequently, should not be removed until immediately prior to mounting the sensor.
  • Page 24 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Installation Proline Promag 50 2.5.3 Installing the high-temperature version (with PFA lining) The high-temperature version has a housing support for the thermal separation of sensor and transmitter.
  • Page 25 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Installation 2.5.4 Tightening torques for threaded fasteners (Promag P) Please note the following: • The tightening torques listed below are for lubricated threads only.
  • Page 26 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Installation Proline Promag 50 Nominal diameter EN (DIN) Threaded Max. tightening torque [Nm] fasteners [mm] Pressure rating [bar] PTFE PN 25 20 × M 33 –...
  • Page 27 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Installation Promag P tightening torques for JIS Nominal diameter Max. tightening torque [Nm] [mm] Pressure rating Threaded fasteners PTFE 4 × M 16 4 ×...
  • Page 28: Installing The Promag H Sensor

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Installation Proline Promag 50 Installing the Promag H sensor Depending on the order specifications, the sensor is supplied with or without ready-mounted process connections. Mounted process connections are fixed to the sensor with 4 or 6 hexagonal-headed bolts.
  • Page 29 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Installation • Grounding rings, incl. seals, are mounted inside the process connections. The face-to-face length is not affected. Installing the grounding rings...
  • Page 30: Installing The Transmitter Housing

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Installation Proline Promag 50 Installing the transmitter housing 2.7.1 Turning the transmitter housing Turning the aluminum field housing Aluminum field housing for non-Ex area £...
  • Page 31 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Installation 2.7.2 Turning the onsite display Press in the side latches on the display module and remove the module from the cover plate of the electronics compartment.
  • Page 32 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Installation Proline Promag 50 Pipe mounting " Caution! mm (inch) Danger of overheating! If the device is mounted on a Ø 20…70 warm pipe, make sure that the housing temperature (Ø...
  • Page 33: Post-Installation Check

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Installation Post-installation check • Is the measuring device damaged (visual inspection)? • Does the device correspond to specifications at the measuring point, including process temperature and pressure, ambient temperature, minimum fluid conductivity, measuring range, etc.?
  • Page 34: Wiring

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Wiring Proline Promag 50 Wiring Warning! Risk of electric shock! Components carry dangerous voltages. • Never mount or wire the measuring device while it is connected to the power supply.
  • Page 35: Connecting The Various Housing Types

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Wiring Connecting the various housing types Wire the unit using the terminal assignment diagram inside the cover. 3.1.1 Compact version...
  • Page 36: Connecting The Remote Version Connecting Cable

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Wiring Proline Promag 50 Connecting the remote version connecting cable 3.2.1 Connecting cable for Promag W, P and L Connecting cable termination Terminate the signal and coil current cables as shown in the figure below (Detail A).
  • Page 37 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Wiring 3.2.2 Promag H connecting cable Connecting cable termination Terminate the signal and coil current cables as shown in the figure below (Detail A).
  • Page 38 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Wiring Proline Promag 50 3.2.3 Connecting cable connection S1 E1 E2 S2GND E S n.c. n.c. n.c. n.c. n.c. n.c. E1 E2 GNDE...
  • Page 39: Potential Equalization

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Wiring Potential equalization Perfect measurement is only ensured when the medium and the sensor have the same electrical potential. Most sensors have a reference electrode installed as standard, which guarantees the required potential connection.
  • Page 40: Degree Of Protection

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Wiring Proline Promag 50 Degree of protection The devices meet all the requirements for IP 67. After mounting in the field or service work, the following points have to be observed to ensure that IP 67 protection is retained: •...
  • Page 41: Hardware Settings

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Hardware settings Hardware settings This section only deals with the hardware settings needed for commissioning. All other settings (e.g. output configuration, write protection, etc.) are described in the associated Operating Instructions on the CD-ROM.
  • Page 42 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Hardware settings Proline Promag 50 PROFIBUS Device address range: 0 to 126 OFF ON Factory setting: 126 Miniature switches for device address Example shown:...
  • Page 43: Terminating Resistors

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Hardware settings Terminating resistors Note! If the measuring device is used at the end of a bus segment, termination is required.
  • Page 44: Commissioning

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Commissioning Proline Promag 50 Commissioning Switching on the measuring device On completion of the installation (successful post-installation check), wiring (successful post-connection check) and after making the necessary hardware settings, where applicable, the permitted power supply (see nameplate) can be switched on for the measuring device.
  • Page 45: Operation

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Commissioning Operation 5.2.1 Display elements Display lines/fields Main line for primary measured values Additional line for additional measured +48.25 xx/yy variables/status variables +3702.6 x...
  • Page 46: Navigating Within The Function Matrix

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Commissioning Proline Promag 50 Navigating within the function matrix > 3 s – – – – A0007562 → Enter the function matrix (starting with measured value display) →...
  • Page 47: Calling The Commissioning Quick Setup

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Commissioning Calling the Commissioning Quick Setup All the functions needed for commissioning are called up automatically with the Quick Setup.
  • Page 48: Software Settings

    Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Commissioning Proline Promag 50 Software settings 5.5.1 Device address Has to be set for measuring devices with the following communication methods: • PROFIBUS DP/PA → device address range 0 to 126, factory setting 126 The device address can be configured via: •...
  • Page 49 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Commissioning Endress+Hauser Page 49 of 52 Page 49 of 52 Q-Pulse Id Q-Pulse Id VM454 Active 30/09/2014 Active 30/09/2014...
  • Page 50 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Commissioning Proline Promag 50 Endress+Hauser Page 50 of 52 Page 50 of 52 Q-Pulse Id Q-Pulse Id VM454 Active 30/09/2014 Active 30/09/2014...
  • Page 51 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction Proline Promag 50 Commissioning Endress+Hauser Page 51 of 52 Page 51 of 52 Q-Pulse Id Q-Pulse Id VM454 Active 30/09/2014 Active 30/09/2014...
  • Page 52 Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instruction KA00026D/06/EN/14.11 71154524 FM+SGML 9.0 Page 52 of 52 Page 52 of 52 Q-Pulse Id Q-Pulse Id VM454 Active 30/09/2014 Active 30/09/2014...

Table of Contents