Mounting

16
5
Mounting
5.1

Installation conditions

• Moisture must not penetrate the housing when mounting the device, establishing the
electrical connection and during operation.
• Do not clean or touch process isolating diaphragms with hard and/or pointed objects.
• Do not remove process isolating diaphragm protection until shortly before installation.
• Always tighten the cable entry firmly.
• Point the cable and connector downwards where possible to prevent moisture from
entering (e.g. rain or condensation water).
• Protect housing against impact.
• For devices with gauge pressure sensor, the following applies:
NOTICE
If a heated device is cooled in the course of a cleaning process (by cold water, for
example), a vacuum develops for a short time causing moisture to penetrate the
sensor via the pressure compensation element (1).
Device could be destroyed!
In the event of this happening, mount the device in such a way that the pressure
compensation element (1) is pointing downwards at an angle or to the side, if possible.
1
5.2

Influence of orientation

Any orientation is possible. However, the orientation may cause a zero point shift, i.e. the
measured value does not show zero when the vessel is empty or partially full.
A
PTP31B PTP33B
Process membrane axis is
horizontal (A)
Calibration position, no effect
Ceraphant PTC31B, PTP31B, PTP33B IO-Link
1
B
Process membrane pointing
upwards (B)
Up to +4 mbar (+0.058 psi)
1
1
C
Process membrane pointing
downwards (C)
Up to –4 mbar (–0.058 psi)
Endress+Hauser
A0022252
A0024708