3.2.3

Orientation

Vertical orientation
Recommended orientation with upward direction of flow (View A). Entrained solids sink
down. Gases rise away from the measuring sensor when fluid is not flowing. The piping
can be completely drained and protected against build-up.
Horizontal orientation
In the recommended installation range in a horizontal installation position (View B), gas
and air accumulation at the pipe cover and problematic build-ups at the bottom of the
pipe have a minor influence on the measurement.
Fig. 6:
Installation position (A = vertical, B = horizontal, C = recommended installation range max. 120°)
3.2.4

Inlet and outlet runs (Clamp On version)

If possible, install the sensor well clear of assemblies such as valves, T-pieces, elbows,
etc. If several flow obstructions are installed, the longest inlet or outlet run must be con-
sidered. Compliance with the following requirements for the inlet and outlet runs is rec-
ommended to ensure measuring accuracy.
1
2
3
Fig. 7:
Inlet and outlet runs (Clamp On version)
1 = Valve; 2 = Pump; 3 = Two pipe bends in different directions
≥ 15 x DN
≥ 5 x DN
≥ 40 x DN
≥ 20 x DN
≥ 40 x DN
3 Installation
15