Di-8P X - Eaton EDR-5000 Nstallation, Operation And Maintenance Manual

Distribution
Hide thumbs Also See for EDR-5000:
Table of Contents

Advertisement

DI-8P X

Name of the Assembly group:
DI-8P X1
Device Parameters of the Digital Inputs on DI-8P X
Parameter
Description
Nom Voltage
Nominal voltage of the digital inputs
Inverting 1
Inverting the input signals.
Debouncing Time 1 A change of the state of a digital input will only be
recognized after the debouncing time has expired
(become effective). Thus, transient signals will not be
misinterpreted.
Nom Voltage
Nominal voltage of the digital inputs
Inverting 2
Inverting the input signals.
EDR-5000
Setting range
24 V dc,
48 V dc,
60 V dc,
110/120 V dc,
230/240 V dc,
110/120 V ac,
230/240 V ac
Inactive,
Active
No Debouncing
Time,
20 ms,
50 ms,
100 ms
24 V dc,
48 V dc,
60 V dc,
110/120 V dc,
230/240 V dc,
110/120 V ac,
230/240 V ac
Inactive,
Active
www.eaton.com
IM02602007E
Default
Menu path
110/120 V dc
[Device Para
/Digital Inputs
/DI-8P X1
/Group 1]
Inactive
[Device Para
/Digital Inputs
/DI-8P X1
/Group 1]
20 ms
[Device Para
/Digital Inputs
/DI-8P X1
/Group 1]
110/120 V dc
[Device Para
/Digital Inputs
/DI-8P X1
/Group 2]
Inactive
[Device Para
/Digital Inputs
/DI-8P X1
/Group 2]
76