Program Mode

By means of the Program Mode , parameter settings can be locked against any changes as long as one or all of the
breaker(s) are in the » CLOSED« position. The Program Mode can be activated within the [System Para/General
Settings/Program Mode Bypass] menu.
»Both Bkr Open« - Parameter changes require all breakers to be in the » OPEN « state.
»Either Bkr Open or Close« - Parameter changes do not require the breaker to be in the » OPEN« state.
Unlike, if the Program Mode is used for Motor Protection devices, the user has the following options:
»Motor Stop« - Lock parameter changes, if the motor is not in the » STOP« state.
This ensures, that parameter changes can only be done while the motor stands still (zero speed).
»Either Motor Stopped or Running« - Parameter changes do not require the motor to be in the » Motor stop« state.
Bypass of the Program Mode
The program mode can be bypassed by means of the Direct Control Parameter » Program Mode Bypass« . The
protective device will fall back into the program mode either:
Directly after a parameter change has been saved, else
10 minutes after the bypass has been activated.