Eaton EDR-5000 Nstallation, Operation And Maintenance Manual page 427

Distribution
Hide thumbs Also See for EDR-5000:
Table of Contents

Advertisement

Parameter
Description
Ack TripCmd
Ack TripCmd
Trigger1
Open Command to the Breaker if the state of the
assigned signal becomes true.
Trigger2
Open Command to the Breaker if the state of the
assigned signal becomes true.
Trigger3
Open Command to the Breaker if the state of the
assigned signal becomes true.
Trigger4
Open Command to the Breaker if the state of the
assigned signal becomes true.
Trigger5
Open Command to the Breaker if the state of the
assigned signal becomes true.
Trigger6
Open Command to the Breaker if the state of the
assigned signal becomes true.
Trigger7
Open Command to the Breaker if the state of the
assigned signal becomes true.
Trigger8
Open Command to the Breaker if the state of the
assigned signal becomes true.
Trigger9
Open Command to the Breaker if the state of the
assigned signal becomes true.
Trigger10
Open Command to the Breaker if the state of the
assigned signal becomes true.
EDR-5000
Setting range
1..n, Assignment
List
1..n, Trip Cmds
1..n, Trip Cmds
1..n, Trip Cmds
1..n, Trip Cmds
1..n, Trip Cmds
1..n, Trip Cmds
1..n, Trip Cmds
1..n, Trip Cmds
1..n, Trip Cmds
1..n, Trip Cmds
www.eaton.com
IM02602007E
Default
Menu path
-.-
[Control
/Bkr
/Trip Manager]
50P[1].TripCmd
[Control
/Bkr
/Trip Manager]
50P[2].TripCmd
[Control
/Bkr
/Trip Manager]
50P[3].TripCmd
[Control
/Bkr
/Trip Manager]
51P[1].TripCmd
[Control
/Bkr
/Trip Manager]
51P[2].TripCmd
[Control
/Bkr
/Trip Manager]
51P[3].TripCmd
[Control
/Bkr
/Trip Manager]
50X[1].TripCmd
[Control
/Bkr
/Trip Manager]
50X[2].TripCmd
[Control
/Bkr
/Trip Manager]
51X[1].TripCmd
[Control
/Bkr
/Trip Manager]
51X[2].TripCmd
[Control
/Bkr
/Trip Manager]
427