Eaton EDR-5000 Nstallation, Operation And Maintenance Manual page 583

Distribution
Hide thumbs Also See for EDR-5000:
Table of Contents

Advertisement

Auto Reclosing States during manual breaker closing.
Bkr State
Pos CLOSE
1
Pos OPEN
0
Manual Breaker Close
1
0
AR - Module states
Protection Trip while Manual Close Blocking time is Timing
What happens if while the timer manual close block time is timing down the protective device gets a trip signal?
While the timer manual close block time is timing, any trip during this time period trips the breaker. The manual close
block timer does not care about that and timing continues until it times out.
After it times out, the AR-module looks at the breaker status again and sees that the breaker is open. The AR goes to
the »STANDBY« state, no autoreclosure is possible. Note: The AR Does Not go to »LOCKOUT« state!)
Bkr State
Pos CLOSE
1
Pos OPEN
0
Manual Breaker Close
1
0
Protection Trip
1
0
AR - Module states
Standby
Standby
EDR-5000
t-ManualCloseBlock
t-Man Close Blo
t-ManualCloseBlock
t-Man Close Blo
www.eaton.com
IM02602007E
t
t
Ready
t
t
t
Standby
583