Device Planning Parameters of the Low-Voltage-Ride-Through
Parameter
Description
Mode
Mode
Setting Group Parameters of the Low-Voltage-Ride-Through
Parameter
Description
Function
Permanent activation or deactivation of module/element. Inactive,
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Blo TripCmd
Permanent blocking of the Trip Command of the
module/element.
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Measuring Mode
Measuring/Supervision Mode: Determines if the phase-
to-phase or phase-to-earth voltages are to be
supervisioned
EDR-5000
Options
Do not use,
Use
Setting range
Active
Inactive,
Active
Inactive,
Active
Inactive,
Active
Phase to Ground,
Phase to Phase
www.eaton.com
Default
Menu path
Do not use
[Device Planning]
Default
Menu path
Inactive
[Protection Para
/<1..4>
/LVRT [1]
/General Settings]
Inactive
[Protection Para
/<1..4>
/LVRT [1]
/General Settings]
Inactive
[Protection Para
/<1..4>
/LVRT [1]
/General Settings]
Inactive
[Protection Para
/<1..4>
/LVRT [1]
/General Settings]
Phase to Ground [Protection Para
/<1..4>
/LVRT [1]
/General Settings]
IM02602007E
776