Eaton EDR-5000 Nstallation, Operation And Maintenance Manual page 209

Distribution
Hide thumbs Also See for EDR-5000:
Table of Contents

Advertisement

Parameter
Description
Start: 7
Start recording if the assigned signal is true.
Start: 8
Start recording if the assigned signal is true.
Auto overwriting
If there is no more free memory capacity left, the oldest
file will be overwritten.
Post-trigger time
The post trigger time is settable up to a maximum of 50%
of the Maximum file size setting. The post-trigger will be
the remaining time of the "Max file size" but at maximum
"Post-trigger time"
Pre-trigger time
The pre trigger time is settable up to a maximum of 50%
of the Maximum file size setting.
Max file size
The maximum storage capacity per record is 10 seconds,
including pre-trigger and post-trigger time. The waveform
recorder has a total storage capacity of 120 seconds.
EDR-5000
Setting range
1..n, Assignment
List
1..n, Assignment
List
Inactive,
Active
0 - 50%
0 - 50%
0.1 - 10.0s
www.eaton.com
IM02602007E
Default
Menu path
-.-
[Device Para
/Recorders
/Waveform rec]
-.-
[Device Para
/Recorders
/Waveform rec]
Active
[Device Para
/Recorders
/Waveform rec]
20%
[Device Para
/Recorders
/Waveform rec]
20%
[Device Para
/Recorders
/Waveform rec]
2s
[Device Para
/Recorders
/Waveform rec]
209