Eaton EDR-5000 Nstallation, Operation And Maintenance Manual page 43

Distribution
Hide thumbs Also See for EDR-5000:
Table of Contents

Advertisement

3-phase, 3-wire IG Measured
A
IA
Zero Sequence Current
Transformer: Measures the
ground current (sum of the three
phase currents ). Can be used for
measuring the ground current in
isolated and compensated
networks. The shield is to be
returned through the zero
sequence current transformer .
Three-phase Current Measurement ; Inom Secondary = 1 A.
Ground Current Measuring via Zero Sequence CT ; IGnom Secondary = 1 A.
Warning!
The shielding at the dismantled end of the line has to be put through the zero sequence
current transformer and has to be grounded at the cable side .
B
C
IB
IC
EDR-5000
IA'
IB'
IC'
IX'
IR calc = IA + IB + IC
IX meas = IG
www.eaton.com
IM02602007E
X?.
1A
1
5A
2
IA
N
3
1A
4
5A
5
IB
N
6
1A
7
5A
8
IC
9
N
1A
10
5A
11
IX
12
N
43