Eaton EDR-5000 Nstallation, Operation And Maintenance Manual page 574

Distribution
Hide thumbs Also See for EDR-5000:
Table of Contents

Advertisement

3 Ready
An activated autoreclose function is considered to be in »R
The breaker is in closed position;
The Manual-Close-Block-timer elapses after a breaker manual/remote close operation;
The autoreclose function is not initiated from any initiate (start) functions; and
No external or internal AR blocking signals are present.
4 Run (Cycle)
The »R
« state can only be reached if the following conditions are fulfilled:
UN
The autoreclose was in »R
The breaker was in closed position before;
No external or internal AR Blocking signals exist; and
At least one of the assigned initiate functions is true (triggers the Autoreclosure).
If the autoreclose gets into the »R
automatomatically with several subordinate states which will be described in detail in the next section (AR Cycle).
An autoreclose start is only possible if the autoreclose function is in Ready state.
« state before;
EADY
A complete autoreclose process with multi-shot reclosing will be accomplished
inside the Run state.
« state, the autoreclose function transfers its control to a »R
UN
EDR-5000
« state when all of the following conditions are true:
EADY
www.eaton.com
IM02602007E
« state control
UN
574