Device Planning Parameters of the Trip Circuit Monitoring Module

Parameter
Description
Mode
Mode
Global Protection Parameters of the Trip Circuit Monitoring Module
Parameter
Description
Mode
Select if trip circuit is going to be monitored when the
breaker is closed or when the breaker is either open or
close.
Input 1
Select the input configured to monitor the trip coil when
the breaker is closed.
Input 2
Select the input configured to monitor the trip coil when
the breaker is open. Only available if Mode set to
"Either".
Only available if: Mode = Either
ExBlo1
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
ExBlo2
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
EDR-5000
Options
Do not use,
Use
Setting range
Closed,
Either
1..n, Dig Inputs
1..n, Dig Inputs
1..n, Assignment
List
1..n, Assignment
List
www.eaton.com
Default
Menu path
Use
[Device Planning]
Default
Menu path
Closed
[Protection Para
/Global Prot Para
/Supervision
/TCM]
DI-8P X1.DI 1
[Protection Para
/Global Prot Para
/Supervision
/TCM]
-.-
[Protection Para
/Global Prot Para
/Supervision
/TCM]
-.-
[Protection Para
/Global Prot Para
/Supervision
/TCM]
-.-
[Protection Para
/Global Prot Para
/Supervision
/TCM]
IM02602007E