Eaton EDR-5000 Nstallation, Operation And Maintenance Manual page 121

Distribution
Hide thumbs Also See for EDR-5000:
Table of Contents

Advertisement

Parameter
Description
Disarm Mode
CAUTION! RELAYS DISARMED in order to safely
perform maintenance while eliminating the risk of taking
an entire process off-line. (Note: Zone Interlocking and
Supervision Contact cannot be disarmed). YOU MUST
ENSURE that the relays are ARMED AGAIN after
maintenance.
t-Timeout DISARM
The relays will be armed again after expiring of this time.
Only available if: Mode = Timeout DISARM
Force Mode
By means of this function the normal Relay Output States
can be overwritten (forced) in case that the Relay Output
is not in a disarmed state. The relays can be set from
normal operation (relay works according to the assigned
signals) to "force energized" or "force de-energized"
state.
t-Timeout Force
The Output State will be set by force for the duration of
this time. That means, for the duration of this time, the
Relay Output does not show the state of the signals that
are assigned on it.
Only available if: Mode = Timeout DISARM
EDR-5000
Setting range
Permanent,
Timeout
0.00 - 300.00s
Permanent,
Timeout
0.00 - 300.00s
www.eaton.com
IM02602007E
Default
Menu path
Permanent
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/DISARMED
/RO-6 X5]
0.03s
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/DISARMED
/RO-6 X5]
Permanent
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Force RO
/RO-6 X5]
0.03s
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Force RO
/RO-6 X5]
121