Advertisement

Parameter
Description
Q min QV
Trigger for the Reactive Power (Positive Phase
Sequence System)
Only available if: QV-Method = Pure Reactive Power
Superv
t1-QV
First timer. If this timer has elapsed, a trip signal will be
issued to the (local) energy resource.
t2-QV
Second timer. If this timer is elapsed, the an trip signal
will be issued to the PCC (Point of Common Coupling)
Input States of the Q->&V< Module
Name
Description
ExBlo1-I
Module Input State: External Blocking1
ExBlo2-I
Module Input State: External Blocking2
EDR-5000
Setting range
0.01 - 0.20VAn
0.00 - 2.00s
0.00 - 4.00s
www.eaton.com
Default
0.05VAn
0.5s
1.5s
Assignment via
[Protection Para
/Global Prot Para
/Q->&V<]
[Protection Para
/Global Prot Para
/Q->&V<]
IM02602007E
Menu path
[Protection Para
/<1..4>
/Q->&V<
/Decoupling]
[Protection Para
/<1..4>
/Q->&V<
/Decoupling]
[Protection Para
/<1..4>
/Q->&V<
/Decoupling]