Parameter
Description
Force Mode
By means of this function the normal Relay Output States
can be overwritten (forced) in case that the Relay Output
is not in a disarmed state. The relays can be set from
normal operation (relay works according to the assigned
signals) to "force energized" or "force de-energized"
state.
t-Timeout Force
The Output State will be set by force for the duration of
this time. That means, for the duration of this time, the
Relay Output does not show the state of the signals that
are assigned on it.
Only available if: Mode = Timeout DISARM
Input States of RO-4ZI X
Name
Description
RO1.1
Module Input State: Assignment
RO1.2
Module Input State: Assignment
RO1.3
Module Input State: Assignment
RO1.4
Module Input State: Assignment
RO1.5
Module Input State: Assignment
EDR-5000
Setting range
Permanent,
Timeout
0.00 - 300.00s
www.eaton.com
Default
Permanent
0.03s
Assignment via
[Device Para
/Relay Outputs
/RO-4Z X2
/RO 1]
[Device Para
/Relay Outputs
/RO-4Z X2
/RO 1]
[Device Para
/Relay Outputs
/RO-4Z X2
/RO 1]
[Device Para
/Relay Outputs
/RO-4Z X2
/RO 1]
[Device Para
/Relay Outputs
/RO-4Z X2
/RO 1]
IM02602007E
Menu path
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Force RO
/RO-4Z X2]
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Force RO
/RO-4Z X2]