59N - Neutral Overvoltage - Eaton EDR-5000 Nstallation, Operation And Maintenance Manual

Distribution
Hide thumbs Also See for EDR-5000:
Table of Contents

Advertisement

Commissioning: Aux. Overvoltage
Object to be tested:
Aux. Overvoltage protection elements.
Necessary components:
One-phase AC voltage source;
Timer for measuring of the tripping time; and
Voltmeter.
Procedure (for each element):
Testing the threshold values
For testing the threshold and dropout values, the test voltage at the measuring input for the voltage has to be increased
until the relay is activated. When comparing the displayed values with those of the voltmeter, the deviation must be wi-
thin the permissible tolerances.
Testing the trip delay
For testing the trip delay a timer is to be connected to the contact of the associated trip relay. The timer is started when
the limiting value of the tripping voltage is exceeded and it is stopped when the relay trips.
Testing the dropout ratio
Reduce the measuring quantity to less than 97% of the trip value. The relay must only dropout at a minimum of 97% of
the trip value.
Successful test result
The measured threshold values, trip delays, and dropout ratios comply with those specified in the adjustment list.
Permissible deviations/tolerances can be taken from the Technical Data.

59N - Neutral Overvoltage

Available elements:
59N[1] ,59N[2]
This is the 59 device for the Neutral Overvoltage settings (this element works based on fundamental).
All elements are identically structured.
EDR-5000
www.eaton.com
IM02602007E
634