Switch Direction Control
Switching commands are validated before execution. When the switchgear is already in the desired position, the switch
command will not be issued again. An opened breaker cannot be opened again. This also applies for switching
command at the HMI or via SCADA.
Anti Pumping
By pressing the CLOSE command softkey only a single switching CLOSE impulse will be issued independent, how long
the softkey is actuated. The switchgear will close only once per close command.
Direct Commands of the Control
Parameter
Description
Res Bwear Sl
Resetting the slow breaker alarm
Breaker
Ack TripCmd
Acknowledge Trip Command
Global Protection Parameters of the Control
Parameter
Description
CinBkr-52a
The breaker is in CLOSE-position if the state of the
assigned signal is true (52a).
CinBkr-52b
The breaker is in OPEN-position if the state of the
assigned signal is true (52b).
Ready
Breaker is ready for operation if the state of the assigned
signal is true. This digital input can be used by some
protective elements (if they are available within the
device) like Auto Reclosure (AR), e.g. as a trigger signal.
EDR-5000
Setting range
Inactive,
Active
Inactive,
Active
Setting range
1..n, Dig Inputs
1..n, Dig Inputs
1..n, Dig Inputs
www.eaton.com
IM02602007E
Default
Menu path
Inactive
[Operation
/Reset]
Inactive
[Operation
/Reset]
Default
Menu path
DI-8P X1.DI 5
[Control
/Bkr
/Pos Indicatrs
Wirng]
DI-8P X1.DI 6
[Control
/Bkr
/Pos Indicatrs
Wirng]
-.-
[Control
/Bkr
/Pos Indicatrs
Wirng]
425