①
PTC inputs, suitable for motors in the Ex-zone or Non-Ex-Zone
②
If you use these inputs, remove the jumper.
③
If you use these inputs, remove the 100 Ω resistor.
④
Four-way distribution terminal for 24 V
⑤
In the case of equipped peripheral board 3 / 4, the supply of the digital inputs ‑X2:8 to 16 is changed over. The digital
inputs are now supplied from ‑X2:1/3 instead of ‑X2:51/55.
Figure 8-37
Control cable terminals for "peripheral board 4" application
This application fulfills the requirements concerning the terminal assignment and the inverter
functions which have been developed by the Normengemeinschaft für Mess- und
Regelungstechnik, in short NAMUR. These specifications can be found in the NAMUR NE37
guideline.
Perform the wiring of the terminal block in accordance with the terminal plan. Remove the
factory-installed jumpers according to the "Standard" application if the respective application
requires this.
8.8.2.3
Mode setting of the NAMUR application
The mode setting for the NAMUR application is "Namur 1". Refer to the section "NAMUR mode
settings" (Page 90) for more detailed information.
Installation and operating instructions Sinamics G180
Operating Instructions, 05/2013, 4BS0751-001
Operation
8.8 Examples / Applications
127