Standard mode settings

8.2.1

Mode "std siss"

(D)
(S)
Figure 8-3
Control behavior for "Local" (dynamic)
● Enter the command "Speed On" and "Speed Off" using the <On> and <Off> buttons on the
● Make the setpoint value setting using the <down arrow> and <up arrow> buttons.
● Reset errors by pressing the buttons <S+I> simultaneously.
Control behavior for "Remote" (static)
● Control the operation of "Speed on" with a switch at –X2:10.
● Enter the setpoint via control cable terminal block –X2 with analog setpoint value 1.
● When required use the reversing input –X2:16.
"Local" and "Remote" mode
● "Emerg. stop (NC)": If you open the contact at –X2:15, the drive decelerates down to 0
● "Reset" (NO): Reset errors and "Emerg. stop" using a 24 V pulse at –X2:14.
● "Controller release, static " (NC) ‑X2:8: Enable the inverter using a permanent contact. The
Installation and operating instructions Sinamics G180
Operating Instructions, 05/2013, 4BS0751-001
Dynamic: Pushbutton mode
Static: Switch mode
Assignment of the control cable terminals for "std siss" mode
display.
speed along the braking ramp for emergency stop. The inverter clears all self-holding
functions.
drive coasts to a stop if you open the contact. The inverter clears all self-holding functions.